Technical Specifications - Johnson Controls VA9310 Serie Instrucciones De Instalación

Ocultar thumbs Ver también para VA9310 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical Specifications

VA9310 Series Electric Non-Spring Return Valve Actuator
Product Description
Power Requirements
Transformer Sizing
requirements
Input Signal/Adjustments
Control Impedance
Feedback Signal
Rotation Range
Rotation Time
Rotation Time Autocalibration
Cycles
Audible Noise
Electrical Connections
Conduit Connections
Ambient Conditions
Fluid Temperature Limits
(Actuator and Valve Assembly)
Enclosure
Dimensions
Shipping Weight
Compliance
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
VA9310 Series Electric Non-Spring Return Valve Actuators Installation Instructions
VA9310-HGA-2: On/Off and floating mode
24 VAC (19.2 to 28.8 VAC) at 50/60, Class 2 (North America) or SELV (Europe), 6 VA
running. 24 VDC (21.6 to 28.8 VDC) Class 2 (North America) or SELV (Europe)
<6 VA
19.2 to 28.8 VAC at 50/60 Hz or 24 VDC
±10 Class 2 (North America) or SELV
(Europe)
4.7k ohm
Mechanically limited to95±3
90 seconds
35 seconds
100,000 full stroke cycles; 2,500,000 repositions
<35 dBA at 39-13/32 in. (1 m)
120 in. (3.05 m) UL 444 Type CMP plenum rated cable with 19 AWG cable (0.75 mm²)
conductors and 0.25 in. (6 mm) ferrule ends
1/2 in. NPSM (13 mm) threaded conduit connectors with M9300-100 conduit connector
Operating: -22 to 140F (-30 to 60C), 90% RH, noncondensing
-
-
Storage:
40 to 185F (
40 to 85C), 95% RH, noncondensing
VG12x1 and VG18x1 Series: 23 to 203F (-5 to 95C)
VG12x5 and VG18x5 Series: -22 to 212F (-30 to 100C)
VG12x5 and VG18x5 Series with M9000-561 Thermal Barrier Installed: -22 to 284F
(-30 to 140C) water; 15 psig (103 kPa) at 250F (121C) saturated steam
IP54/NEMA 5
See Table 2.
2 lb (0.9 kg)
United States:
UL Listed, CCN XAPX, File E27734, Under UL 60730, UL 60730-2-14,
Plenum Rated (UL 2043).
Canada:
UL Listed, CCN XAPX7, File E27734; Under CAN/CSA E60730 and CAN/CSA-E60730
Europe:
CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and Low
Voltage Directive.
IEC 60730-1: Automatic Electrical Controls for Household and Similar Use, Part 1:
General Requirements and IEC 60730-2-14, Automatic Electrical Controls for Household
and Similar Use; Part 2 - Particular Requirements for Electric Actuators
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
10
VA9310-HGA-2: Proportional mode
0 (2) to 10 VDC or 0 (4) to 20 mA with field
furnished 500 ohm 1/4 W resistor
Offset: 0 to 10 VDC
SPAN: 2 to 10 VDC
100k ohm
0 (2) to 10 VDC

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Va9310-hga-2

Tabla de contenido