7 – Wiring
7-8 AC Input/Output Wiring (Parallel UPS – Single Input)
Parallel Redundancy Warnings:
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1
redundancy ). Do not attempt to link more than two UPS
systems via parallel redundancy.
The UPS systems must have the same rating and capacity
for parallel redundancy installation. Attempting to link
dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Follow the steps in
1
in the diagram.
2
Connect the included parallel redundancy cable
redundancy port
B
7-9 AC Input/Output Wiring (Parallel UPS – Dual Inputs)
Parallel Redundancy Warnings:
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1
redundancy ). Do not attempt to link more than two UPS
systems via parallel redundancy.
The UPS systems must have the same rating and capacity
for parallel redundancy installation. Attempting to
link dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Follow the steps in
1
in the diagram.
Connect the included parallel redundancy cable
2
B
redundancy port
200706017 93-2688 SU manual 4C.indd 21
200706017 93-2688 SU manual 4C.indd 21
(continued)
Section
7-7, wiring the UPS systems as shown
to the parallel
A
of each UPS system.
Section
7-7, wiring the UPS systems as shown
A
to the parallel
of each UPS system.
1
B
2
1
B
2
21
1
2
3
4
5
B
6
A
7
8
9
10
11
12
B
A
13
14
11/29/2007 2:02:42 PM
11/29/2007 2:02:42 PM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartonline su40kxSmartonline su60kxSmartonline su80kx

Tabla de contenido