Installation and configuration of a stand-alone system
Select the option corresponding to the battery type installed and confirm by clicking "OK". Save
the changes.
For more information about the compatible lithium batteries, see the "List of lithium
batteries approved for the INGECON SUN STORAGE 1Play" available on the
Ingeteam website.
If the option selected is Lead-Acid the following parameters must be set:
A wrong configuration of these parameters can reduce battery life.
Setting
V NOMINAL
V MINIMUM
CAPACITY 20 h
CAPACITY 5h
I CHARGE
I DISCHARGE
V ABSORPTION
V FLOTATION
V EQUALIZATION
T EQUALIZATION
It is recommended to install a PT100 sensor (3-wire) to measure the temperature and thus
optimize the lead-acid battery charge and extend its life. The PT100 sensor should be placed in
the center of the side wall of a battery located in the middle of the battery bank. The following
parameter must be configured:
Parámetro
TEMP. COMP.
To activate the compensation temperature, enter via the Display:
Menu > Configuration > Battery > Battery Type > Lead-Acid > PT100 Battery Sensor
Once configured, save the changes.
2. AC loads output
Next, configure the parameters of the AC loads output. Enter via the Display:
Enter the following parameters:
Rated voltage of the battery bank (V).
Minimum voltage of the battery bank to avoid severe discharges stopping the supply
to the loads (V). If this parameter is not available from the battery manufacturer, a
voltage of 90-95% of the V NOMINAL is recommended.
C20 capacity specified by the battery manufacturer (Ah).
C5 capacity specified by the battery manufacturer (Ah).
Maximum charge current of the battery bank (A).
Maximum discharge current of the battery bank (A).
Absorption charge voltage of the battery bank, specified by the battery manufacturer
(V). If this parameter is not available from the battery manufacturer, a voltage of
120% of the V NOMINAL is recommended.
Flotation charge voltage of the battery bank, specified by the battery manufacturer
(V). If this parameter is not available from the battery manufacturer, a voltage of
113% of the V NOMINAL is recommended.
Equalization charge voltage of the battery bank, specified by the battery manufacturer
(V). If the battery does not support equalization, this parameter must be configured
with the V ABSORPTION value.
Duration of equalization charge of the battery bank, specified by the battery
manufacturer (minutes).
Compensation temperature of a cell (-mV/ºC/Cell), specified by the battery
manufacturer. The default value is -4mV/ºC/Cell.
Menu > Configuration > Inverter
Explanation
Explicación
Ingeteam