Lutron EcoSystem C5-BMJ-16A Guia De Instalacion página 3

La caja de conexión del módulo de potencia
Ocultar thumbs Ver también para EcoSystem C5-BMJ-16A:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EcoSystem Power Module / Junction Box Mount | Install Guide
Step 3: Mounting the Module
A. Using two screws from the junction box, attach the
module to the junction box.
B. Be sure all power wires are completely inside the
junction box before tightening the mounting screws.
C. Turn on breaker to energize the module.
D. Attached ballast(s) or loads will turn on to full light
output.
0 Hz
50 /6
~
27 7
V
ax .
10 0–
A M
16
O N
O N
T R
T R
L U
L U
R
TO
IN DI
CA
s
it ha
W ER
tio n un
PO
:C au
r
On
po we
ni ng
nc tio
t fu
Of f: is no
er ly
pr op
lig ht
lig ht
D ay
D ay
so r
S en
NOTE: If lamp(s) do not turn on, verify that the power
(PWR) indicator LED is on; (STAT) indicator will blink if
no communication is present.
Step 4: Wiring EcoSystem Bus
• The EcoSystem Bus Supply controls up to
64 ballasts and ballast modules. EcoSystem Bus
wiring may be run daisy chain, t-tap, and/or star
pattern.
• Bus wiring may be either Class 1 or Class 2.
– Class 1: Low voltage bus wiring may be run with
mains voltage to any fixture the bus is controlling.
NOTE: If wired Class 1, all Class 2 markings
must be removed from the link section of
the product. For more information, please read
Application Note #142
(www.lutron.com/applicationnotes).
– Class 2: Low voltage bus wiring must be
separated from all mains and Class 1 wiring.
• Consult all applicable national and local codes for
compliance.
• Lutron recommends using two different colors for
E1 and E2 (EcoSystem Bus) wire. This helps prevent
bus wiring mistakes.
Use the following guidelines for wiring the EcoSystem
Bus to the module:
A. DO NOT WIRE LIVE. Interrupt power to the
module and the EcoSystem Bus Supply before wiring
and/or servicing the EcoSystem Bus.
B. Connect EcoSystem Bus wires E1 and E2 to
module terminals E1 and E2.
C. Energize the EcoSystem Bus Supply only. Verify that
18 V- is present at the E1 and E2 terminals on the
module.
D. Energize the module.
E. If there is no power/communication on the link, the
status (STAT) LED will blink once per second.
Customer Assistance: 1 .844.LUTRON1
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
C5-BMJ-16A
Power Indicator (PWR)
Indicateur de puissance (PWR)
Indicador de Alimentación (PWR)
On: Unit is powered
On: l'unité est alimentée
Encendido: unidad tiene corriente
Off: Unit is not powered
Off: l'unité n'est pas alimentée
Apagado: unidad no tiene corriente
or is malfunctioning
ou est dysfonctionnelle
o no está funcionando correctamente
Status Indicator (STAT)
Indicateur d'activité (STAT)
Indicador de estado (STAT)
Solid: Circuit Level
Plein: Niveau de circuit
Sólido: Nivel del Circuito
Pulse: No communication
Impulsion: Aucune
Pulsante: No hay comunicación
communication
EcoSystem
TM
Class 2 Sensors
Class 2 Link
Capteurs Classe 2
PWR
STAT
Lien Classe 2
Sensores Clase 2
Enlace Clase 2
E1
E2
E1: Purple
E2: Purple/White
Wire Size and Bus Length
EcoSystem Bus length is limited by the wire gauge
used for E1 and E2 as follows:
Wire Gauge
Bus Length (max)
2
12 AWG (4.0 mm
) 2200 ft (671 m)
2
14 AWG (2.5 mm
) 1400 ft (427 m)
2
16 AWG (1.5 mm
) 900 ft (275 m)
2
18 AWG (1.0 mm
) 570 ft (175 m)
Step 5: Wiring Sensor Inputs
If sensors are wired to the module, follow these
guidelines:
• Refer to sensor specifications for proper wire gauge
and maximum wire distances between the sensor
and the module.
• All sensors and wallstations are Class 2 low voltage.
Do not combine any sensor wiring with mains wiring.
• Follow all national and local electrical code
restrictions when wiring Class 2 devices.
• Wire sensors as instructed by each sensor's
instruction sheets.
• Programming of each sensor and wallstation
is performed via the EcoSystem Programmer
(C-PDA-CLR)
• Power Module can power only 1 of each type of
sensor (occupancy, IR, and daylight).
(see next page for wiring diagrams)
3
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
C5-BMJ-16A
Power Indicator (PWR)
Indicateur de puissance (PWR)
Indicador de Alimentación (PWR)
On: Unit is powered
On: l'unité est alimentée
Encendido: unidad tiene corriente
Off: Unit is not powered
Off: l'unité n'est pas alimentée
Apagado: unidad no tiene corriente
or is malfunctioning
ou est dysfonctionnelle
o no está funcionando correctamente
Status Indicator (STAT)
Indicateur d'activité (STAT)
Indicador de estado (STAT)
Solid: Circuit Level
Plein: Niveau de circuit
Sólido: Nivel del Circuito
Pulse: No communication
Impulsion: Aucune
Pulsante: No hay comunicación
communication
EcoSystem
TM
Class 2 Sensors
Class 2 Link
Capteurs Classe 2
PWR
STAT
Lien Classe 2
Sensores Clase 2
Enlace Clase 2
E1
E2
To additional EcoSystem
modules, ballasts, and the
EcoSystem Bus supply
®

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ecosystem c5-xpj-16a

Tabla de contenido