Troubleshooting - Test D, Minimum Motor Speed Error - Norcold N1090 Serie Manual De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Troubleshooting, cont'd.

Troubleshooting - Test D, Minimum Motor Speed Error

START
Perform Diagnostic Prechecks.
Leave DC supply connected and
remove unit from its enclosure.
Inspect unit ventilation. Max
operational ambient temperature is
131° F (55° C). Is ventilation adequate?
Is the unit free from an overload of hot
items?
Yes
Check the voltage at the DC
connector. Is the voltage within
range?
12 VDC: 10.4 VDC -15.4 VDC
Yes
Is unit overloaded?
No
Is fan running and the coils clean and
not restricted?
Yes
Replace cooling unit.
Modelos N1090/ Modèles N1090/ Modelos N1090
12
, test unit.
No
Repair DC supply voltage, test unit.
No
Reduce load on unit.
Yes
Replace power control module.
No
Four 1/4 second flashes, pause, repeat.
Four (4) 1/4 second fl ashes, pause,
repeat.
Possible Cause:
If the refrigeration system is too heav-
ily loaded, the motor can not maintain
minimum speed (1850 rpm).
NOR000726-4b
Refrigerator Service Manual / Manuel d'entretien du réfrigérateur / Manual de servicio del refrigerador

Publicidad

Tabla de contenido
loading

Tabla de contenido