Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
12
www.ecoflam-burners.com
1
2
VERSION P
E
T
A
L I
2
Regulating the combustion of the one-
stage burner
• position the air valve in the fully open set-
ting (pos. 4).
(for particularly low power only, if the re-
duction of air is not sufficient with the head
in position 1, reduce the opening of the air
valve).
• dose the air by moving the combustion
head (figure) to suit the power required (as
shown in figure).
• dose the gas by regulating the gas ramp
(see figure in the ramp manual).
Firing head setting (1).
To act on the screw in fi gure:
• turn Allen key till you reach the
D
E
T
A
L I
1
requested value (index 1-5).
420010679400