Mount the sensor above and in the centre of the door, on a hard vibration-free
surface. (See Fig. 1 to 5)
Fig. 1 Mounting height (h) must be between 1.8 to 3.0 m.
h
D2
Fig. 2 Horizontal distance to door (a) maximum 0,5 m.
Fig. 3 Vertical distance from sensor to the door (b) maximum 10 cm.
Fig. 4 Sensor alignment: The sensor must be mounted on a wall parallel to
the door. The sensor can accept a deviation of +3 degrees.
Mounting the Sensor
Sensor
placement
height (h)
1800 mm
2200 mm
3000 mm
D1
W1
Presence zone
Motion zone
Depth
Width
motion zone
motion zone
(D1-D2)
(W1)
2040 mm
2460 mm
2490 mm
3000 mm
3400 mm
4100 mm
Depth
presence
zone (D2)
420 mm
510 mm
700 mm
5