Be careful not to short circuit the system when the supply phases are inverted!
SAFETY STRIP (EDGE - COM) - Safety function - PL "b" according to EN13849-1
If it intervenes during opening, it inverts the movement and closes for 2 seconds and then
stops.
If it intervenes during closing, it inverts the movement and opens for 2 seconds and then
stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the gate to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation at least every
6 months.
SAFETY STRIP ALARM
After the inversion given by the intervention of the safety edge, the gate stops in alarm mode
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing
any push button.
TESTING THE SAFETY STRIP equipment
The DIP10 ON enables to test the safety strip equipment. The test is performed every time the
gate completes a full opening. The test is available only if the safety strip device is equipped
with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the A+TEST and
A- outputs (DIP10 ON). Automatically, every time the gate completes a full opening, just
before closing, the control board switches OFF the A+TEST and A- power supply output for a
very short time. While the safety strip power supply is switched OFF, if everything is working
fine the safety strip contact (EDGE - COM) must open. In case the test fails, no other gate
manoeuvre will be allowed and the alarm state will be signalled by both the Blinker and the
Buzzer, if installed, which will remain on for 5 minutes
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP10 MUST BE LEFT
OFF.
STOP BUTTON - Safety function - PL "b" according to EN13849-1
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed contact could be
connected in series to the COM wire of the opened and the closed limit switches.
This contact works like a STOP button to interrupt any gate manouver.
FUNCTIONING IN DEAD MAN MODE WHEN ONE OF THE SAFETY DEVICES IS FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or
remain engaded for more than 60 seconds, the K BUTTON and PEDESTRIAN commands will
work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the led DL1.
With the blinking of the led DL1, the opening and closing operation are allowed only with the
command button pressed and held. The radio commands and that of automatic closing, will
be excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio commands and
automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety strips
(or photocells) the photocells (or safety strips) still work by interrupting the operation
in progress.
The dead-man operation is only an emergency operation which must be activated
for a very short period and with the complete installation at sight so to have a
secure and safe control of the system. As soon as possible however, the failing
safety devices must be repaired and activated.
FLASHING LIGHT
Connect the flashing light to J7 flashing light outputs, use flashing lights ACG7059 and bulbs
of 40W maximum.
NB: This electronic K board can only supply power to FLASHING LIGHTS with inbuilt flashing
circuit.
PRE-FLASHING function
The DIP 5 in the ON position enables the pre-flashing, the FLASHING LIGHT and BUZZER
starts working 3 seconds before every movement of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the FLASHING LIGHT, the BUZZER
and the motor will start at the same time.
BUZZER (COM.+ BUZZER-)
The current supplied to the Buzzer will be 200 mA at 24Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz
intermittently. Only during the alarm situations (safety strip) the buzzing will almost be
constant.
GATE OPEN INDICATOR (A negativo - LSC) - 3 W max
It is turned ON when the gate is open or partially open, it is turned OFF only when the gate
is completely closed.
N.B.: connect in series to the indicator a resistance of 2K2.
WE RECOMMEND NOT TO OVERLOAD THE INDICATORS OUTPUT OTHERWISE THE GATE
FUNCTIONING COULD BE COMPROMISED OR THE CONTROL BOARD COULD BE DAMAGED.

TECHNICAL SPECIFICATIONS

Temperature range
Humidity
Power supply voltage
Frequency
Interruptions in electricity supply
Maximum load of motor outputs
Maximum load of blinker output with resistive load
Maximum control board absorption (without accessories) 33 mA
Current available for photocells and accessories
IP protection grade
Control board weight
Dimensions
TECHNICAL RADIO SPECIFICATIONS (model CRX)
Reception frequency
Impedance
Sensitivity
Time of excitation
Time of discharge
Memory available
Maximum load of radio receiver output
- All inputs shall be used as clean contacts without earthing, because the power supply is
generated in the card and is structured in such a way to guarantee the respect of double
and reinforced insulation to the elements under voltage
- All inputs are managed by a programmed circuit that carries out a self-control every time
the gate is operated.
TROUBLESHOOTING
After having carried out all connections, by carefully following the layout and having
positioned the gate in intermediate position, check the correct ignition of LEDS DL3, DL4,
DL7, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL3
switched off
Faulty opening limit switch
DL4
switched off
Faulty closing limit switch
DL7
switched off
Faulty photocells
DL8
switched off
Faulty safety edge (In case the edge is not connected, carry out
jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening the
green DL6 LED switches on and that during closing the red DL5 LED switches on.
If not, invert clamps V and W on the motor terminal board.
23
G
B
-10 ÷ +55°C
< 95% without
condensation
230V~ ±10% (120V / 60Hz
upon request)
50/60 Hz
20ms
1CV
40W
0,4A±15% 24Vdc
IP54
0,55 kg
130 x 50 x 115 mm
433,92MHz
52 OHM
>2,24µV
300ms
300ms
60 codes (30 for complete
opening and 30 for pedestrian
opening)
200mA 24Vdc