Preparation; Wiring Diagram - Utilitech 7113-01-L Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

PREPARATION

Helpful Tools (not included): Electric Drill, Wood Screws
WARNING: Turn off electricity at breaker box before beginning installation.
Carefully remove unit from carton.
Check area above installation location to be sure that wiring can run to the planned location and that
duct work can be run and the area is sufficient for proper ventilation.
Inspect duct work and wiring before proceeding with installation.
Before installation, provide inspection and future maintenance access at a location that will not interfere
with installation work.
You may need the help of a second person to install this fan; one person on the attic side and one on
the room side.
Note: Installations may vary depending on how the previous bath fan was installed. Supplies necessary
for the installation of your bath fan are not all included; however, most are available at your local
home improvement or hardware store.
DIMENSION REQUIREMENTS
Ceiling
Opening (L)
Opening (W)
9.4 in.

WIRING DIAGRAM

LIGHT HOUSING
Up to 13 Watts
Up to 13 Watts
Automatic terminal
switch
Capacitor
for long
life of
MOTOR
montor
FAN HOUSING
Ceiling
Ceiling
Opening (H)
9.4 in.
7.4 in.
to 120V/60Hz
Junction box
QUICK CONNECTOR INSTRUCTIONS
To be sold only with installation instructions.
WARNING:
codes. Turn OFF power before removing or installing connectors.
WARNING:
CAUTION:
installation instructions below.
NOTE:
The connector is reusable on solid wires of the same wire gage or
to switch
smaller. Do not reuse the connector on stranded wires.
to neutral
• Strip wires 3/8"-1/2"
to ground
• Grip the wire firmly and push
the stripped end of the wire into
the open port of the connector.
Use only one conductor
per port.
Black wire
• Verify the stripped end of the
to switch
wires is fully inserted to the
back of the connector.
White wire
to neutral
Green wire
to ground
NOTE:
Important wire information. Maximum temperature rating 105˚C
(221˚F). 600 volts maximum for building wire and 1000 volts maximum for
building wire and 1000 volts maximum in signs and lighting fixtures.
The acceptable wire range includes: Solid: 12-18 AWG.
5
Wiring must comply with all appliable electrical
COPPER TO COPPER ONLY. Do not use Aluminum wire.
Accessory part (quick connector) should meet
House
wires
Quick
connect
Product
wires
Lowes.com

Publicidad

Tabla de contenido

Solución de problemas