Technical data
Type
Power supply
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Nominal stroke length * See type plate
Additional functions *
* Programmable with software SCS
Running speed and forces
Normal operation =
SHEV- fast running =
KA 34: 300** N, 11,8 mm/s =
"-HS" KA 34 12,2 mm/s
(with tensile force (1/2 nominal load) 16,1 mm/s)
KA 54: 500** N, 11,8 mm/s =
"-HS" KA 54 13,3 mm/s
(with tensile force (1/2 nominal load) 17,2 mm/s)
** + approx. 20 % switch-off reserve (temporary)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
8/120
KA-BSY+
KA 34/xxx-BSY+
24 VDC / ±15% / 1,0 A
300 N
2000 N
>10 000 double strokes
30 % (With cycle time 10 minutes)
Aluminium powder-coated (~RAL 9006)
IP 32
(With covering stoppers delivered with bracket sets)
-5 ... +75°C
30 min / 300°C
Closing edge protection activated (3 stroke repeatings); Locking relief activated
=
=
KA 54/xxx-BSY+
24 VDC / ±15% / 1,4 A
500 N
English
Beside
closing edge
99.823.89 2.4/12/13