Lamborghini Caloreclima PM/2E Serie Manual De Instalación Y Manteniemiento página 57

Quemadores a gas con dos llamas
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The function of the minimum gas pressure switch is to prevent the burner from starting or to stop it when it is
running if the gas pressure is not at the minimum required; it must be calibrated to 40% lower than the gas
pressure value when operating at maximum flow rate.
CALIBRATION OF MAXIMUM GAS PRESSURE SWITCH (ON REQUEST)
The maximum gas pressure switch serves to put the burner in blocking mode if the gas pressure exceeds the
pre-set value. Set the combustion head pressure to 15% more than the nominal capacity required at the time
of installation.
PRESSURE SWITCH Model: GW 50 - LGW 10 A2P
Model
55 PM/2-E
70 PM/2-E
90 PM/2-E
140 PM/2-E
210 PM/2-E
Take off the cover and turn dial (A)
Air pressure
switch - model
DUNGS
LGW 10 A2P
DUNGS
LGW 10 A2P
DUNGS
LGW 10 A2P
DUNGS
LGW 10 A2P
DUNGS
LGW 10 A2P
Pressure tap
Setting range
millibar
switch - model
1 - 10
1 - 10
1 - 10
1 - 10
1 - 10
Gas pressure
Setting range
DUNGS
GW 50
DUNGS
GW 50
DUNGS
GW 50
DUNGS
GW 50
DUNGS
GW 50
57
millibar
2,5 - 50
2,5 - 50
2,5 - 50
2,5 - 50
2,5 - 50

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

55pm/2e70pm/2e90pm/2e140pm/2e210pm/2e

Tabla de contenido