Luces LED de estado
Códigos de diagnóstico del tablero IGN.
Hay dos luces LED en el tablero IGN que proveen estado e
información de diag nóstico. Ver Tabla 7 para una descripción
de los códigos de luices LED.
Tabla 7. Indicadores LED de diagnóstico de IGN
Status LED
Steady OFF
Check Power or Failed Board 2 Flashes
Slow Flash Rate Normal, No Call for Heat
Fast Flash Rate
Not used
Steady ON
Normal, No Call for Heat
Fast Flash Rate: The LED will flash on for 1/4 second, and off for 1/4 second
Slow Flash Rate: The LED will flash on for 3/4 second, then off for 1/4 second.
The pause between groups of fast flashes is 3 seconds.
IGN Diagnostic Indicators Flash Codes
3 Flashes Pressure switch problem detected
4 Flashes
5 Flashes
6 Flashes Flame Rollout Switch open
7 Flashes Thermostat miswired; W1 & W2
Guía Instalación
*
Liteport LED
System Lockout: Failed to detect or
sustain flame
High Limit switch protection device
open
Flame sensed and gas valve not
energized or flame sensed and no "W"
signal
Página 27