As this unit is equipped with an inverter, installing a phase
advancing capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating accident due to high-frequency waves. Therefore, never
install a phase advancing capacitor.
CAUTION
Be sure to install the required fuses or circuit breakers.
14.2. Connecting power supply and interunit wiring
■
Secure the earth wire to the stop valve attachment plate so that
it does not slide.
■
Secure the earth wire to the stop valve attachment plate one
more time along with the electric wiring and the inter-unit wiring.
■
Lay the electrical wiring so that the front cover does not rise up
when doing wiring work and attach the front cover securely.
V3
7
4
8
5
6
1
Switch box
2
Stop valve attachment plate
3
Earth
4
Cable tie
5
Wiring between units
6
Power supply and earth wiring
2
1
1
Power supply, earth wiring, and if applicable: bottom plate heater
wire
2
Wiring between unit
Installation manual
16
1
2
W1
3
3
3
7
4
8
5
6
2
1
2
1
■
When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knockout hole.
(See figure 3)
1
Wire
2
Bush
3
Nut
4
Frame
5
Hose
A
Inside
B
Outside
When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knockout hole from
cutting the wires.
■
Follow the electric wiring diagram for electrical wiring works
(delivered with the unit, located at the inside of the front plate).
■
Form the wires and fix the cover firmly so that the cover may be
fit in properly.
14.3. Precautions on wiring of power supply and
inter-unit wiring
■
Use a round crimp-style terminal for connection to the power
supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following
instruction.
1
Round pressure terminal
2
Cut out section
3
Cup washer
1
2 3
-
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
-
When connecting wires of the same gauge, connect them
according to the below figure.
■
Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.
■
Over-tightening the terminal screws can damage the screws.
■
See the table below for tightening torques for the terminal
screws.
Tightening torque (N•m)
M4 (X1M)
M5 (X1M)
M5 (EARTH)
■
Refer to the installation manual attached to the indoor unit for
wiring of indoor unit, etc.
■
Attach an earth leakage circuit breaker and fuse to the power
supply line. (See figure 6)
1
Earth leakage circuit breaker
2
Fuse
3
Remote controller
■
In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.
1.2~1.8
2.0~3.0
3.0~4.0
RRLQ011~016CAV3+W1
Outdoor unit for air to water heat pump