operating addresses, Address 0 = input, Address 1 = frame output) once the frame has been
opened for input, it will have to be opened for output before carrying out a new input.
Repeat the procedure to restore the previous configuration.
B) LAMP/CORT (Anti-Collision (pedestrian) function):
The control unit is supplied by the manufacturer with the Anti-collision (pedestrian) Function
disabled. If you wish to enable the function, proceed as follows: check that extended menu
2 is enabled (T. MOT. and T. PAUSA LEDs start flashing simultaneously), use the SEL key to
move to the flashing LAMP/CORT LED then press the SET key: at that point the LAMP/CORT
LED will light up steady and programming is complete. The control unit will now operate in
Anti-Collision (pedestrian) mode.
If you wish to enable the Anti-Collision (pedestrian) function for the closing phase only, repeat
the operation described above, pressing the SEL key twice (making the LAMP/CORT LED flash
quickly). Repeat the procedure if you wish to restore the previous configuration.
RESET:
To reset the default configuration of the control unit, press the SEL and SET keys simulta-
neously; all RED indicator LEDs will switch on and after a few seconds off again.
DIAGNOSTICS:
Control input test:
On each low voltage control input, the control unit uses a LED signal to make the status
readily known.
Operating logic: when a LED is on it means the input is closed, when a LED is off it means
the input is open.
MANAGING PROGRAMMING LEDS:
After 3 minutes of inactivity in the programming procedure, the control unit will automati-
cally switch off the programming LEDs to save energy. The LEDs will light up, depending on
the previously set programs, only when the SEL or SET keys are pressed or when a motion
command has been received.
Το πλήρες κείμενο της δήλωσης συμμόρφωσης ΕΕ είναι
TERMINATION BUS RS-485:
διαθέσιμες στην ακόλουθη διεύθυνση στο Διαδίκτυο:
The communication BUS is by standard RS485. It is possible to make connections with cable
lengths up to 100 m.
In case of communication problems it is recommended to move the Jumper J1 to 1-2
http://www.seav.it
(insertion of the terminating resistor) on devices located at the ends of the links:
J1 pos. 1-2 = inserted termination resistance.
J1 pos. 2-3 = not inserted terminating resistor (default).
The full text of the EU Declaration of Conformity is
available at the following Internet address:
http://www.seav.it
Nota : Rev. 3.1 Aggiornamento globale alla Rev. 3.0
18
Rev. 3.1 03/08/2017