8 - MAINTENANCE AND CLEANING
8.1 - CLEANING
Before proceeding with any maintenance and cleaning
intervention, it is essential to disconnect all the power
circuits and/or disconnect all the main switches.
• Cleaning of the sheet steel panels must be carried out only with cloths dampened with water and soap.
• In case of tenacious stains, damp the cloth with a 50% mixture of water and denatured alcohol or with
specific products.
• Once cleaning is complete, dry the surfaces with care.
Do not use a chemically treated or antistatic cloth to clean the appliance.
Do not use gasoline, solvent, polish or similar solvents.
These products could cause the breakage or deformation of the plastic surface.
8.2 - PERIODIC MAINTENANCE
Periodic maintenance is essential in order to maintain the heat pump always efficient, safe and reliable over
time. Maintenance can be carried out periodically by the Technical Assistance Service, which is technically
authorized and prepared and also has, if necessary, original spare parts available.
The maintenance plan that OLIMPIA SPLENDID's Technical Assistance Service
or the maintenance technician must respect, with annual periodicity, includes
the following operations and checks:
• Expansion vessels pressure check (check pressure on the label of the ex-
pansion vessel).
• Water circuit filling.
• Presence of air in the water circuit.
• Efficiency of safety devices.
• Electrical power voltage.
• Electrical absorption.
• Electrical connections tightening.
• Cleaning of fans grilles and external unit battery fins.
• Check for presence of dirt on the metallic net filters.