6.2 - REMOTE CONTROL
It is possible to control some functions of the appliance remotely.
Parameter "ADDR220"
0 = remote control disabled
1 = remote control through serial
2 = remote control through free contacts
6.2.1 - Serial
The control from serial is only possible through SIOS CONTROL domotic.
If control from serial is enabled, some functions on the main screen are disabled (mode of operation, timer).
6.2.2 - Free contacts
The connections of the contacts must be carried out on the terminal box of the internal unit electronic board.
The contacts must be closed on terminal L.
If control from contacts is enabled, some functions on the main screen are disabled (mode of operation).
Terminal
terminal 1
terminal 2
terminal 3
terminal 4
terminal 5
DHW terminal
TA terminal
terminal 8
terminal 9
EN - 38
Description
Cooling mode enabling
Heating mode enabling
ECO setpoint enabling
Night function enabling
COMMON CONNECTED TO N
DHW input can be connected to a free contact for enabling of domestic hot water
production.
If ADDR228=1, the production of domestic hot water is disabled with contact open,
enabled with contact closed.
TA input can be connected to a free contact of a chronothermostat or to the contacts
in parallel chiller/boiler of the electronic controls of the fan coils BI2 and BI2+.
When the contact is closed, all cooling, heating and domestic water production func-
tions are enabled.
When the contact is open, only domestic water production remains active.
Input from SMART GRID or photovoltaic FTV1
Input from SMART GRID or photovoltaic FTV2