Progress
06_ Detect
outdoor
components
07_ Detect
indoor
components
08_ Confirm
preheated
compressor
09_Confirm
status of valve of
ODU
10_Debugging
completed status
5 Common Malfunctions and Troubleshooting
WARNING
① If there is abnormal condition (e.g. unpleasant smell), turn unit off and disconnect power
immediately. Then contact Gree authorized service center. If unit continues operation
despite the abnormal condition, it may get damaged and lead to electric shock or fire
hazard.
② Do not repair the air conditioner by yourself. Improper maintenance may lead electric
shock or fire hazard. Please contact Gree authorized service center for maintenance.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
The Ducted Split Type Air-Conditioning Units(Inverter Series) Installation and Operation Manual
Description of each stage of debugging progress
Debugging Code
LED
Display
Display Code
Code
06/corresponding
Display
error code
repeatedly
Display
06/oC
repeatedly
07/
Display
corresponding
repeatedly
error code
Display
07/oC
repeatedly
Display
08/U0
repeatedly
Display
08/oC
repeatedly
Display
09/U4
repeatedly
OFF
On
Instruction for Code and Operating Method
Error of components of ODU. Except ―0 6‖, others will
flickeringly
display
corresponding
eliminating all the errors, it will automatically enter into the
next step. If the ODU should be powered off for the
debugging, after re-energizing the unit, please conduct
debugging from the above 01 step.
No component of ODU is found in the system, it will enter
into the next step 10 seconds later.
Error of components of IDU are detected. For example, the
IDU displays d5 and d6 simultaneously, the nixie tube will
repeatedly display ―0 7‖, ―d 5‖, ―d 6‖. After eliminating all the
errors, it will automatically enter into the next step. If the
ODU should be powered off for the debugging, after
re-energizing the unit, please conduct debugging from the
above 01 step.
No component of IDU is found in the system, it will
automatically enter into the next step 5 seconds later.
Insufficiency preheating of compressor. The nixie tube will
display as the left until the preheating time for compressor
has reached 8 hours, then press SW3 can skip over the
waiting time, and automatically enter into the next step 2
seconds later. (Note: if the preheating time for the
compressor is less than 8 hours, there may be a risk for
damage of compressor, please conduct with care)
If the ODU is continuously energized for ≥8h, or the
continous 8-hour energizing time in the last time till now is
less than 2 hours (it requires clock chip), it means the
preheating is completed, the system will automatically enter
into the next step 2 seconds later.
The system shuts down due to malfunction. The error
module nixie tube repeatedly display ―0 9‖ and ―U6‖, other
module nixie tubes repeatedly display ― 09‖ and ―J 0‖. If erroe
occurs, please check if the valve is opened, and at the same
time check if the connecting pipes between different
modules are correctly connected.
If all the modules shut down, then all the module nixie tube
will display ―0 9‖ and ―o C‖ for once.
The whole unit has gone through the debugging, the system
is in stand-by status.
17
error
code.
After