Configuration manual
5. APPLICAT application type Screen. Select
the application type H in this screen. To
do this press the joystick once.
At the bottom of the display PRG appears,
indicating that it is possible to modify the
value.
Move the joystick in any of the 4 directions
until TYP.H appears. Press the joystick
once to accept.
6. Move to the SYS system type selection
screen using the joystick. Press the
joystick once (the PRG indication will
appear on the bottom of the display). Move
the joystick in any of the 4 directions until
1P (in single-phase installations) or 3P.N
(in three-phase installations) is reached.
Press the joystick once to accept.
7. In the case of the A65+ wattmeter, move
to the transformation ratio selection screen
CT RATIO (from 1.0 to 60.00 k).
For example, if the primary current of the
transformer is 3000 A and the secondary
current is 5 A, the transformation ratio is
600
8. Move to the ADDRESS node number
screen using the joystick. Press the
joystick once (the PRG indication will
appear on the bottom of the display). Move
the joystick in any of the 4 directions to
indicate the wattmeter´s node number.
Press the joystick once to accept.
9. Accepting this gains access to the BAUD
RATE configuration screen. Press the
joystick again (the PRG indication will
appear on the bottom of the display). Move
the joystick in any of the 4 directions to
select 9600 bps. Press the joystick once
to accept.