ELECTING BETWEEN AMBIENT REGULATION AND DUCT REGULATION
Program pre-set for:
- Regulation of output temperature (by duct sensor) "CTRL output".
In this configuration there is no ambient sensor.
Room temperatures can be regulated using a room temperature sensor. This type of regulation is called
"CTRL ambient". In this configuration the duct sensor acts as a output cut-off control.
To change configuration:
Select menu: Configuration
From the main screen:
- press q
Reg. new air intake
06:11:09
16:09
System: active
Sp: 23.0 Act: 23.4°C
Until the following screen appears:
Actual/setpoint
Input/output
Time setting
Setting
Manual/auto
u
Configuration
Access rights
when the pointer is beside
"Configuration"
- press u
For custom settings, see the "Corrigo E ventilation user's manual" or contact us
F
AULT MESSAGES ON CONTROL PANEL
In the event of a fault, a red LED flashes on the control panel and an error message indicates the problem
detected (pressing the red button the control panel displays the message in the event that it is not already
shown).
Example: filter is clogged
After replacing the filter this message will no longer be displayed
Main faults
Display
Fan error, NA
Filter clogged
Output T too high
Overheating in Elec.
heater battery
- Select; Ctrl function
Inputs/outputs
u
Ctrl function
Object type
Pump control
q
- press u
p
:
Description
Air intake fan error
Filter clogging threshold
reached
Output temperature is too high
Heater battery overheating
safety activated
Setting function
Ctrl function
Mode:
CTRL output
Choice of type of control:
CTRL output
CTRL output
CTRL ambient
CTRL return
Ambient / Output
Return / Output
In the present case, select:
"CTRL ambient"
Filter clogged
20 Nov 11:14 classC
Cause
ü
Differential pressure switch in heater
battery not detected or illegal threshold
ü
Filter clogged or illegal threshold
ü
Temperature above 60°C (this error
disappears once the system is
stabilized)
ü
One of the safety thermostats is triggered
at the threshold of 75°C or 120°C (if the
fault persists, the safety thermostat must
be manually reset to 120°C for the
electric heater battery)