Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).

For the installer

2

About the box

2.1

Indoor unit

WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable. Refer to the outdoor unit specifications for the
type of refrigerant to be used.
2.1.1
To remove the accessories from the
indoor unit
a
b
g
j
a
Paper pattern for installation (upper part of packing)
b
General safety precautions
c
Indoor unit installation and operation manual
d
Washers for hanger bracket
e
Screws
f
Cable ties
g
Metal clamp
h
Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
i
Drain hose
j
Insulation piece: Small (liquid pipe)
k
Insulation piece: Large (gas pipe)
3

Preparation

3.1

Preparing the installation site

3.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
FFA25~60A2VEB(9)
Split system air conditioners
4P456960-1B – 2018.08
c
d
e
f
h
i
k
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for

installation

in
a
commercial
environment.
▪ Spacing. Mind the following requirements:
a
A
≥1500
≥1500
≥2000
A
Minimum distance to the wall
B
Minimum and maximum distance to the floor (see below)
C
≥295 mm: In case of installation with BYFQ60B
≥300 mm: In case of installation with BYFQ60C
a
Indoor unit
b
Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c
Air fan
d
Static volume (example: table)
▪ Minimum and maximum distance to the floor:
▪ Minimum: 2.5 m to avoid accidental touching.
▪ Maximum: Depends on the air flow directions and the capacity
class. Also make sure the "Ceiling height" field setting
corresponds with the actual situation. See
settings" on
page 9.
4
Installation
4.1

Mounting the indoor unit

4.1.1

Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ Decoration panel. Install the decoration panel always after
installing the unit.
2 About the box
and
light
industrial
b
c
a
d
≥4000
(mm)
"5.1  Field
Installation and operation manual
5