INTRODUCTION

"Albatros RVA46.531" is realized for use as a single boiler regula-
tor or as a zone regulator with a mixing valve or a pump in integrated
systems, using RVA43.222 or RVA47.320 regulators.
It is planned to be integrated in a heat–production system with the
following boilers:
– PLANET (all types)
– PLANET DEWY BFT-BFR, PLANET DEWY 30/50
– DEWY
– MISTRAL 32/xx
– LOGO (all types)
The system utilizes the principle of climate adjustment (based on the
external temperature) for the heating circuit, allowing to control the
production of sanitary hot water (A.C.S.) in combined boilers.
2

CHARACTERISTICS OF THE ALBATROS RVA46.531

Hereunder you'll find the panel that the user will see upon opening the
cover.
2. 1

KEY FUNCTIONS

7
6
DESCRIPTION
1
Room temperature set up knob
2
Buttons for setting the value at the selected parameter
3
Parameter selection buttons
4
Display: the values, set–up and state of operation are displayed
c
a) Symbols – the black bars indicate the state of operation
b) Display during normal control mode or during set–up.
c) Programming line during set–up
68
5
20
14
26
°C
5) Operation mode buttons
Automatic:
– Heating is activated according to the set program.
– Protection functions are active
– Automatic Summer/Winter switching is active
Continuous:
– Heating without a set timing
– Temperature is adjusted using the knob
– Protection functions are active
– Room unit influence is not active
– Automatic Summer/Winter switching is not active
Standby:
– Heating is OFF
– Temperature is adjusted according to the anti–freeze
protection system
– Protection functions are active
– Room unit influence is not active
6) Function key with manual operation LED
– Manual activation of heating in case of a failure of the
control system
– Temperature depends upon the maximum limit of deli-
very setpoint (line 69)
– Heating circuit pump is active (Q2)
– Mixing valve is not fed (Y1/Y2)
7) PC–connection option for error diagnostic and service.
2.2

PARAMETER SETTING LEVELS

4
The parameters that can be set up are of 3 kinds:
3
– end user
2
– installer
– manufacturer (OEM)
1
To enter one of these modes it is necessary to follow the instructions
provided in the following charts.
2.2. 1

User Level

Several set–up options are available to meet the individual require-
ments of the end user: a 7–day heating program option; heating
curve slope, through which the setpoint for the zone delivery tempe-
rature can be modified; Summer/Winter switching temperature;
A.C.S. temperature setpoint (only if connected to a boiler card).
Please refer to Point 10 for the complete list.
Buttons
Explanation
PUSH ONE OF THE "UP/DOWN" SELECTION
1
BUTTONS. THIS WILL LEAD YOU DIRECTLY TO THE
"END USER" PROGRAMMING MODE.
a
PUSH THE SELECTION BUTTONS
2
TO SELECT A LINE
PUSH THE "+/–" BUTTON TO SET UP THE
b
DESIRED VALUE. THE SET VALUE WILL BE
3
STORED WHEN YOU QUIT THE
PROGRAMMING MODE OR MOVE ON TO
ANOTHER LINE.
TO QUIT THE "END USER" PROGRAMMING
4
MODE, PUSH ONE OF THE BUTTONS OF
THE WORKING MODE.