Parameter Setting; I2 Installation: Combined Boiler With High And Low-Temperature Zones - Sime D Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.2. 1

Parameter setting

For the regulator to be able to recognize this installation you need to
set the following parameters as shown in the table.
LOW–TEMPERATURE ZONE:
mixing valve, pump, zone feeler and room unit
Installation ID
– Setting mode = USER
(refer to the "Parameter setting levels" paragraph)
Par
Description
17*
Heating curve slope
* According to the installation type
– Setting mode = INSTALLER
(refer to the "Parameter setting levels" paragraph)
Par
Description
69*
Max. limit of delivery temp. setpoint
96
Input H1
* According to the installation type
NOTE 1: The thermostat for excess temperature has the purpose of
stopping the production of heat in case the water temperature gets
too high and damages the floor. We recommend setting at 45°C.
NOTE 2: When a zone thermostat is required the AUTO led is
blinking. This doesn't therefore indicate a failure.
3.2.2
Verifying the correct recognizing
To make sure the regulator has correctly recognized the installation
on the basis of the input parameters, display the "Installatore" para-
meter on line 53 of the RVA46.531. Installation n° 16 must appear.
Par
Description
53
Type of installation
72
Default values
Setup
15
7,5
Default values
Setup
80
37
0
2
RVA 46.531
16
3.3
I2 INSTALLATION: COMBINED BOILER WITH HIGH
AND LOW–TEMPERATURE ZONES
Characteristics in outline:
– Self–adjusting to the heat requirements
– Automatic Summer/Winter switching
– Climate adjustment with external feeler of the low–temperature zone.
– Zone regulation with mixing valve, pump, zone feeler and room unit
(QAA70) control device through RVA46.531 regulator.
– High temperature zone with fixed point.
– 7–day heating program option.
– 7–day program option for sanitary hot water.
– Automatic operation of the heating/sanitary priority.
– Installation anti–freeze function.
The foreseen components to realize the installation are as follows:
Code
Description
RVA46.531
Zone control regulator
QAA70
Room unit
QAD21/QAZ21
Zone feeler
QAC31
External temperature feeler
Albatros jumper
Quantity
1
1
1
1
1