FUNCTION TESTS

Once the installation of the regulator and all the electrical connec-
tions are done and ready, it is better to check the configuration by
means of the input and output tests, which allow quick identification
of malfunctions and failures.
51
Output test
With this test, all outputs can be checked before the setting at work
of the boiler.
Buttons
Explanation
PUSH BOTH THE LINE SELECTION BUTTONS
1
FOR AT LEAST 3 SECONDS. THIS WILL LEAD
YOU INTO THE OUTPUT TEST
PUSH THE +/– BUTTONS REPEATEDLY
2
TO MOVE ONE STEP FORWARD
ALL OUTPUTS PERFORM THEIR
TEST STEP 0
ACCORDING TO THE CONTROL
TEST STEP 1
3
TEST STEP 2
TEST STEP 3
TEST STEP 4
TO QUIT THE PROGRAMMING MODE
AND THE OUTPUT TEST, PUSH ONE OF
THE WORKING MODE BUTTONS.
4
If no button is pushed for 8 minutes,
the control device will return
automatically to the
last selected working mode.
a
c
a) The bar underneath the symbol indicates the activated output
(pump)
b) The number 2 indicates the actual step of the test.
c) The number 51 indicates the selected setting line.
Line
51
51
SWITCHING FUNCTIONS
MODE
ALL OUTPUTS
OFF/DISABLED
PUMP IS
ACTIVATED (Q2
MIXING VALVE IS
OPEN (Y1)
MIXING VALVE IS
CLOSED (Y2)
b
52
Input test
This is also called "feeler test" and it is used to check the wiring and
the configuration of all the sensors.
Buttons
Explanation
PUSH BOTH THE LINE SELECTION BUTTONS
1
FOR AT LEAST 3 SECONDS. THIS WILL LEAD YOU
INTO THE PROGRAMMING MODE.
PUSH THE "SU" LINE SELECTION BUTTON
2
UNTIL YOU REACH LINE 52. THIS WILL LEAD YOU
INTO THE INPUT TEST.
PUSH THE +/– BUTTONS REPEATEDLY
TO MOVE ONE STEP FORWARD
DELIVERY TEMPERATURE VALUE,
TEST STEP 0
ACQUIRED THROUGH SENSOR B1
EXTERNAL TEMPERATURE VALUE
TEST STEP 1
3
ACQUIRED THROUGH SENSOR B9
TEST STEP 2
TEST STEP 3
TO QUIT THE PROGRAMMING MODE
AND THE INPUT TEST, PUSH ONE OF
THE WORKING MODE BUTTONS.
4
If no button is pushed for 8 minutes,
the control device will return
automatically to the
last selected working mode.
If the sensor is open, – – – will be displayed.
If there is a short circuit, ° ° ° will appear.
c
a
a) The number 1 indicates the actual step of the test.
b) Value of the measured temperature (18 °C)
c) The number 52 indicates the selected setting line.
Line
ROOM TEMPERATURE VALUE,
ACQUIRED THROUGH ROOM
UNIT CONNECTED WITH A6
INPUT H1 (000 / —–)
°C
b
51
52
52
79