• Movements diagonal to the detector are ideal for triggering the device
(a direct and head-on approach makes it more difficult for the device
to detect movement and the range is thus significantly reduced).
• The detector should be positioned according to spatial conditions
and requirements.
GB
• Ensure that the detector has a clear line of sight, as infrared beams
cannot penetrate solid objects.
The presence detector features two separate/light-dependent switching
channels, as well as an HVAC channel that is switched regardless of the
light value.
Information on how to position and align the detector (see fig. 2): The
detector should be mounted in a central position between the strip lights.
Channel 1 must be oriented towards the wall side (dark side of the room)
and channel 2 towards the window side (bright side of the room).
ESYLUX PD-C360i/24 DUOplus series presence detectors consist of
a power and a sensor section. Install the power section in the required
position (fig. 3) and connect the presence detector as shown in the
circuit diagram (fig. 4).
Fig. 4
Master/slave connection for presence detectors: you can connect a
maximum of 10 slave devices to one master device. Ensure that the total
length of the cable used to connect the master to the furthest slave device
does not exceed 100 m, as this may result in switching errors, depending
on the type of installation.
You can adjust the detector's settings using the DIP switches on the
back of the sensor (see the "DIP switch" section in chapter 6). This must
12
be done before the device is activated. Plug the sensor section into
the power section and gently screw in place.
4 • START-UP
Connect the power supply
• This will initiate a warm-up phase of approximately 25 seconds.
The red (light channel 1 = C1), the green (light channel 2 = C2) and the blue
LEDs will flash alternately. The connected lighting will be switched
on during this time.
The detectors are preset to factory settings/remote control and are
therefore immediately ready for use after the warm-up phase.
Overview of the factory settings (DIP switch 3)
Light value for light channel 1
Light value for light channel 2
Time setting for light channel 1 + 2
Time setting for HVAC channel
Mode
5 • OPERATION
Depending on the preset light value, each time movement is detected
the red or green LED will briefly flash twice (the LED can be switched
off - see chapter 8 / Remote control). The presence detector operates
according to its default factory settings.
Factory settings
400 lux
400 lux
5 minutes
1 hour
fully automatic