8 • SETTINGS AND FUNCTIONS VIA MOBIL-PDi/plus REMOTE CONTROL
(FIGS. 6.1 + 6.2)
NOTE: To get the best possible reception, point the remote control at the
detector during programming. Please note that if the sun shines directly
onto the sensor, the standard detection range of approximately 8 m may
be reduced by the sun's infrared rays.
Please take note of the modified remote control (fig. 6.2). All functions
can also be carried out using the previous version (fig. 6.1).
Temporary functions
The functions are carried out as soon as the button has been pressed,
but they are not stored.
Button
Customised setting
Selecting the channel
Selects the appropriate channels.
Switch ON/OFF manually
Switches ON/OFF the lighting of the previously
selected channel C1 - C3.
End the "test" / manual light ON/OFF / time setting function
Return to preset mode
Channels 1 - 3 remain permanently switched on
during test mode.
Each time a movement is detected, the blue mode
LED flashes twice, regardless of the ambient lighting
level. Press the "Reset" button to exit.
Programming
The following functions can only be programmed when the device is
in programming mode. All changes are stored and the functions are
implemented after exiting programming mode.
Button
Customised setting
Enter programming mode
Blue LED lights up to indicate programming mode.
Light channels C1 + C2 are switched on with 100 %
luminous efficiency. The detector's movement sensor
is disabled whilst the device is in programming mode.
Exit programming mode
Blue LED goes out; the settings are now stored. The
detector will now operate automatically according
to the preset values.
NOTE: If programming mode is not exited by
pressing the button, the detector automatically
exits programming mode 10 minutes after the last
button was pressed. All functions set up until this
point will be stored.