Time delay from "dark to light": 5 minutes = red LED lights up for channel 1/
green LED lights up for channel 2.
The "blind" function interrupts the time delay from "light to dark" if the
light value falls below 50 lux and then switches the lighting on at once.
GB
Button S1 – S2/remote control C1 – C2 + light ON/OFF
The presence detector is equipped with a connection for an external
button for each switching channel. This can be used to manually switch
each switching channel on or off, or to temporarily change the light
channel's DIM values.
Manual switch-on
Briefly press S1 – S2/remote control C1 – C2 + light ON/OFF: the lighting will
then remain switched on for as long as the detector continues to detect
movement. The predefined time setting will start once movement is no
longer detected. Once this time has elapsed, the lighting will switch off
and and the detector will revert to the set operating mode.
Manual switch-off
Briefly press S1 – S2/remote control C1 – C2 + light ON/OFF: the lighting will
then remain switched off for as long as the detector continues to detect
movement. The predefined time setting will start once movement is no
longer detected. Once this time has elapsed, the detector will revert to
the set operating mode.
Changing the DIM value
Press S1 – S2 until the required light value is reached. The light value
remains set for as long as the detector continues to detect movement.
The predefined time setting will start once movement is no longer detected.
Once this time has elapsed, the lighting will switch off and the detector
will revert to the set operating mode with the original light value.
14
6 • SETTINGS
DIP switch (Fig. 5)
DIP switch 1: "RC"/"manual"
The switch is set to "RC" in the factory settings. This means that the
device can be operated by remote control. The potentiometers are
disabled when the device is in this mode.
When it is set to "manual", settings can be made using the potentiometers
located on the device. The device cannot be operated by remote
control when it is set to "manual".
DIP switch 1
Time setting (light)
• Control: light values in lux
= light value is approx. 5 lux.
For ease of use, the lux scale is graded according to the area
of application:
• passageways = 1 - 2 (approx. 40 – 200 lux)
• working areas = 2 - 3 (approx. 200 – 600 lux)
• activities requiring a high level of lighting = > 3 (> 600 lux)
Light value
Time setting (HVAC)
= daytime operation