If the ambient lighting level is darker than the preset light value,
the light channel is adjusted to this preset value. C1 will remain on
for as long as movement is detected and as long as the ambient light
value does not exceed the preset light value. However, if the ambient
lighting level is brighter than the preset light value, light channel C1 will
GB
be set to the orientation light value and will switch off after the set
time has elapsed, regardless of whether motion is detected or not.
However, if light is required, the desired brightness value must be set
using the S1 button before the set time elapses. In this case, light channel C1
will remain on for as long as movement is detected, regardless of the
ambient lighting level.
The HVAC channel is switched on when movement is detected, regardless
of the ambient light value. The time settings for the respective channels
will start if movement is no longer detected. Each channel can also be
manually switched on or off using buttons S1 – S2.
Corridor semi-automatic mode for light channel C1
Light is switched on manually using the S1 button, no automatic activation.
If the ambient lighting level is darker than the preset light value, light
channel C1 is adjusted to this preset value. This will remain on for as
long as movement is detected and as long as the ambient light value
does not exceed the respective light value. However, if the ambient
lighting level is brighter than the preset light value, the light channel is
adjusted to 100 % of the luminous efficiency. This will remain on for as
long as movement is detected, regardless of the ambient lighting level.
The HVAC channel is switched on when movement is detected, regardless
of the ambient light value. The time settings for the respective channels
will start if movement is no longer detected. Light channel C1 cannot be
switched off by button. The HVAC channel can be manually switched off
using the S2 button.
16
Orientation light
The orientation light value is 10 % of the full luminous efficiency.
The Mobil-PDi/plus remote control can be used to switch this function
either on or off.
Afterglow feature
The orientation light switches on for an adjustable period of time once
movement is no longer detected and the preset time setting
has elapsed.
Night-light feature
If no movement is detected, the orientation light switches on at the
preset orientation light value when the ambient light level falls below
the preset light value. It remains on until a movement is detected or
until the preset light value is exceeded.
8 • SETTINGS AND FUNCTIONS VIA MOBIL-PDi/plus
REMOTE CONTROL (FIG. 6)
NOTE: To get the best possible reception, point the remote control at the
detector during programming. Please note that if the sun shines directly
onto the sensor, the standard detection range of approximately 8 m may
be reduced by the sun's infrared rays.
Please take note of the modified remote control (fig. 6.2). All functions
can also be carried out using the previous version (fig. 6.1).
Temporary functions
The functions are carried out as soon as the button has been pressed,
but they are not stored.