A -> Normally Open (input activated with GND)
F -> Normally Closed (input activated by removing GND)
BUTTON INPUT -> Exit clearance button
PASSAG SENSOR -> Pass-through sensor
DOOR SENSOR -> Open door sensor
SENSOR BYPASS -> Channel bypass sensor
B) OUTPUTS MENU
RELAY TIME 1-4 (0.5, 1, 2, 3 s)
Determines the retention time, in seconds, of the main relays (channels 1
to 4).
I/Os 5-8
Determines the automatic control of the auxiliary relays (5 to 8):
Off* -> Disabled.
Command -> Activated in conjunction with the main relays.
A. Tampering -> Triggered when the system identifies the event "door
violated" (tampering).
Low battery -> Relay 7 activated when the system identifies a remote control
with low battery. For REC TX, REC TX+TP and REC TX+CTWB modes only.
Parking control -> Activated when the system identifies a access without a
parking space (when Parking Control is active in the MG 3000 Module ).
Relays 5 and 8 for "Entry" and Relays 6 and 7 for "Exit". For REC TX mode
only.
Open Door -> Triggered when the system identifies the "open door" event.
Double Pass -> Triggered when the system identifies two passes through the
pass-through sensor for only one valid activation.
TP Command -> Configures the auxiliary relays for the exclusive use of the
PASSIVE Tag mode, while the main relays are used by the REC TX mode. For
REC TX+TP mode only.
I/Os TIME 5-8 (0.5*, 1 to 98 s, On/Off)
Determines the retention time of the auxiliary relays (5 to 8) in seconds.
BUZZER (on*, off)
Enables sound notifications from the Receiver in normal operating mode.
C) DISPLAY MENU
LED DISPLAY [1, 2] (No*, Yes)
Enables the use of the message display to the Receiver's RS-232 channel.
EFFECT -> Message transition effect
Options: cyclical*, immediate, open R. (right), open L. (left)
MESSAGE TIME -> Display time between messages
Options: 5* to 160 s (5-second interval)
MESSAGE -> Rest message
Option: maximum 8 characters (--NICE--*)