Connection
Connect the 2 sets of L1, L2 and Ground wires (1 Input, 1
2
Output) according to markings on the connectors as seen in
diagram 2. Be sure to connect one set of wires to the input
terminals and the other set to the output terminals.
Slide in and reattach the terminal strip cover with the 3
3
screws from Step 1.
Attach the PDU to the UPS system using 4 screws as seen in
4
diagram 4.
Hardwiring the Transformer Bundle (Input/Output)
SU6000RT4UTF
1.
Plug the XFMR into the UPS.
2.
Connect the transformer to the UPS. This can be a
hardwire connection, outlet connection or both,
provided the combined load does not exceed capacity.
SU12KRT4UHW
See manual included with Parallel PDU for connection,
setup and installation information.
201102161 933070.indb 11
(continued)
2
3
4
L1
G
L2
L
208 / 240V
Input
Set Front Panel Selector Switch to Proper Voltage Before Making Connections
11
G
N
N
G
120V
120V
Output
Output
Branch A
Branch B
3/29/2011 4:34:10 PM