ABB EOHU Serie Boletín De Instrucciones página 17

Ocultar thumbs Ver también para EOHU Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Neutral assembly (optional)
Neutral assembly (EOHXSN78), optional
Install the neutral link on the bottom plate of the safety switch
to the existing threaded holes according to the picture. See
chapter Cabling.
EOHXSN78:
Wire range: (4) #2 - 600 kcmil / 4 x 35 -300 mm
Torque: wire tightening for Cu and Al cables 500 lbs.in / 55.7 Nm
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
2
Failure to follow these instructions will result in death or serious injury.
Instruction Bulletin EOHU367/8J/R/S/SS, 1SCC340040M1401 / A | Installation 1/13
DANGER
1

Publicidad

Tabla de contenido
loading

Tabla de contenido