Bond in accordance
with applicable codes.
3. Make the Electrical Connections – USA
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing
the following procedures.
WARNING: Risk of electric shock. Connect the blower motor to a properly grounded,
grounding-type receptacle protected by a Ground-Fault Circuit-Interrupter (GFCI) or Residual
Current Device (RCD). Do not remove the grounding pin from the plug. Do not use a grounding
adapter.
NOTICE: The blower motor is equipped with a cord and plug. A qualified electrician must install a GFCI-
or RCD-protected, 120 V, 15 A, grounded outlet for the blower. No other load should be on this circuit.
Install an electrical outlet behind the bath, at least 1-1/2" (38 mm) above the subfloor, and within
reach of the 24" (610 mm) power cord.
Plug the blower into this outlet.
Kohler Co.
24" (610 mm) Max. Distance
Between Blower and Outlet
Air Intake
Install a GFCI-protected
120 V, 15 A grounded outlet.
7