OPERATION

SPAN Settings

STAGE 1
Your thermostat is set at the factory to cycle at 1°F
(0.5°C) above and below the set temperature in Stage
1. (Span = 2.) This setting has been designed to pro-
vide a comfortable room temperature under most all
conditions. However, if you find your system cycling
too fast or too slow, then the Span can be adjusted to
modify the cycle time. Refer to the Option Menu Stage
1 Span selection on page 17.
Span = 1. This decreases the cycle time by caus-
ing your system to run shorter.
Span = 3. This increases the cycle time by causing
your system to run longer.
The Span settings remain the same for both HEAT and
COOL.
The Span can be changed at any time and is indepen-
dent of program times or temperatures.
When the thermostat is powered on or the Reset key is
pressed, the Span is reset back to setting 2.