Connecting HART
Typical PLC/mA configuration with HART
Notes:
• Depending on the system
design, the power supply may
be separate from the PLC, or
integral to it.
• Loop resistance (total of cable
resistance plus 250 Ohm
[resistor]) must be less than
550 Ohm for the device to
function properly.
Wiring setups for hazardous area installations
1. Intrinsically Safe wiring
Device nameplate (ATEX/IECEX/INMETRO/C-TICK)
SITRANS LR260
7MLxxxx-xxxxx-xxxx-
BOX 1
Serial No: GYZ / S1034567
Encl.: NEMA / TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Power Rating: 24 V
Nom., 30 V
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
The ATEX certificate listed on the nameplate
can be downloaded from the product page of our website at: www.siemens.com/LR260. Go
to Support > Approvals / Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 11.0153X.
Device nameplate (FM/CSA)
FM/CSA Intrinsically Safe connection drawing number A5E03745229 can be downloaded
from the product page of our website at: www.siemens.com/LR260. Go to Support >
Installation Drawings > Level Measurement > Continuous - Radar.
• For power demands see
• For wiring requirements: follow local regulations.
• Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X /
type 4X / NEMA 6, IP67, IP68 locations.
Instructions specific to hazardous area installations
• Refer to
A5E32106122
SITRANS LR260 (HART) – QUICK START MANUAL
All manuals and user guides at all-guides.com
power
supply
HART
KCC-REM-S49
SITRANSLR
Max., 4 - 20 mA
Loop Voltage versus Loop Resistance
active PLC
R= 250 
HART
communicator
SITRANS LR260
II 1 G D,
1/2 D
, 2 D
Ex ia IIC T4 Ga
Ex ta IIIC T100°C Da
OCP 0017
SIRA 11ATEX2348X
Ex ia IIC T4 Ga
IECEx SIR 11.0153x
Ex ta IIIC T 100°C Da
ARP0108 Ex ia IIC T4 Ga
DNV 12.0081 X
WARNING: Use Cable Rated >100°C
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA – VEJA INSTRUÇÕES
- UTILIZAR CABOS ADEQUADOS PARA TEMPERATURAS >100 °C
on page 19.
on page 9.
HART modem
Ui = 30 V
Ii = 120 mA
Pi = 0.8 W
Ci = 15 nF
Li = 0.1 mH
0891
0518
Page EN-7