SA0051 The machine data for star connection were entered, the motor, however, is connected in delta. For star
operation, change the motor cable connection. For delta operation, check the entered rated motor val-
ues. Repeat the parameter identification.
SA0052 The machine data for delta connection were entered, the motor, however, is connected in star. For
delta operation, change the motor cable connection. For star operation, check the entered rated motor
values. Repeat the parameter identification.
SA0053 A phase asymmetry was measured. Check the cables at the terminals of the motor and the frequency
inverter for proper connection and check the contacts for corrosion.
Code
SF000
No error message exists.
SF001
The value entered for parameter
SF002
The value for parameter
Rated Voltage
376 and
SF003
The value entered for parameter
Correct the value.
SF004
The calculated slip frequency is negative. Correct the values entered for parameters
Rated Frequency
and
SF005
The calculated slip frequency is too high.
Correct the values entered for parameters
SF006
The calculated total output of the drive is lower than the rated power. Correct the value entered for
Rated Mech. Power
parameter
SF007
The set configuration is not supported by the guided commissioning. For parameter
select one of the configurations described in these operating instructions.
Code
SF0011
The main inductance or leakage inductance measurement has failed because the motor has a high slip.
SF0012
Correct the rated motor values in parameters 370, 371, 372, 374, 375 and 376. Carry out the guided
commissioning once again. In case an error message is displayed again, enter the value 110 for pa-
Configuration
rameter
far. Carry out the guided commissioning once again.
SF0021
The measurement of the stator resistance or rotor resistance did not deliver a plausible value. Check
SF0022
the cables at the terminals of the motor and the frequency inverter for proper connection and check the
contacts for corrosion and safe contact. Repeat the parameter identification.
09/08
09/08
Warning messages after Parameter identification
Error messages during Guided commissioning
Meaning / Remedy
Rated Current
Rated Current
371 is too high, referred to parameters
370. Correct the values.
Rated Cosinus Phi
375.
Rated Speed
376.
Error messages after Parameter identification
Meaning / Remedy
30 (sensorless regulation according to U/f-characteristic) if value 410 was set so
371 is too low. Correct the value.
374 is wrong (greater than 1 or smaller than 0.3).
Rated Frequency
372 and
Rated Mech. Power
Rated Speed
372
375.
Configuration
30,
47
47