BURNER ELECTRICAL WIRING
230V
N
N
1
2
3
Valve
Black
D5498
NOTES
2
– Wires of 1 mm
section.
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
– To remove the control-box from the burner,
loosen screw (A) (see figure) and pull
towards the arrow.
– The photoresistance is fitted directly into the
control-box (underneath the ignition-trans-
former) on a plug-in support.
TESTING
Check the shut-down of the burner by opening the
thermostats.
2347
~
50Hz
L
Switch with fuse
6A max.
L
4
5
6
Black
Capacitor
Motor
WARNING
Do not exchange the neutral with the phase.
Remote lock-out lamp
(230V - 0.5A max.), if required
7
8
9
11
M
~
A
RUN OF THE ELECTRICAL CABLE
1 - Cable gland
2 - Cable-clamp
3 - Terminal block
5
GB
Regulating thermostat
T
Limit thermostat
T
with manual resetting
Terminal block of
10
12
control-box 531SE
Heater 55W
3
2
N - Neutral
L - Phase
- Burner-earth
*
S7026