Montage und Bedienungsanleitung Installation, use and maintenance instructions Instrucciones para la instalación, uso y mantenimiento Gas-Gebläsebrenner Forced draught gas burner Quemador de gas de aire soplado Einstufiger Betrieb One stage operation Funcionamiento de una etapa CODE MODELL - MODEL TYP - TYPE CÓDIGO MODELO TIPO...
Página 2
Konformitätserklärung K.E. 8/1/2004 & 17/7/2009 – Belgien Hergestellt von: RIELLO S.p.A. 37045 Legnago (VR) Italien Tel. ++39.0442630111 www.rielloburners.com In den Verkehr gebracht durch: RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel. (053) 769 030 Fax. (053) 789 440 e-mail. info@riello.be URL. www.riello.be Hiermit wird bescheinigt, dass die nachfolgend aufgeführte Geräteserie dem in der CE-Konformitätse-...
ABMESSUNGEN Flansch Brenner ø D5066 Langer Flammkopf auf Anfrage MITGELIEFERTES ZUBEHÖR Stückzahl Beschreibung Schrauben mit Muttern Isolierdichtung Schrauben zur Befestigung der Brenner- haube Kabeldurchführung Scharniereinheit 7-poliger Stecker ZUBEHÖRTEILE SATZ SOFTWAREDIAGNOSE Zur Verfügung steht ein Spezialsatz, der die Lebensdauer des Brenners mittels optischem Anschluss an einen PC erkennt und seine Betriebsstunden, die Anzahl und Typik der Störab- schaltungen, die Seriennummer des Steuergeräts usw.
Página 5
BRENNERMONTAGE Den Flammkopf vom übrigen Brenner durch Entfernen MONTAGE DER SCHARNIEREINHEIT der Mutter (1) und Zurückbewegen der Gruppe (A) trennen. Die Gruppe (B) an der Platte (2) des Heizkessels befe- stigen und die beiliegende Isolierdichtung (3) einfügen. S7392 D5067 BETRIEBSBEREICH D5135 15.000 20.000...
Página 6
ZUSAMMENHANG ZWISCHEN GASDRUCK UND LEISTUNG Für eine maximale Leistung sind 4,6 mbar gemessen an der Muffe mit Brennkammer bei 0 mbar und Gas G20 - Pci = 10 kWh/Nm (8.570 kcal/Nm ) erforderlich. D5136 15.000 20.000 30.000 40.000 50.000 kcal/h Wärmeleistung GASANSCHLUSS–SCHEMA MBC 65 DLE...
ELEKTRISCHE ANSCHLÜSSE ACHTUNG: Nullleiter nicht mit Phase austauschen; sich genau an das angege- ~ 50Hz 230V bene Schema halten und eine gute Erdung ausführen. Der Leiterquerschnitt muss mindestens 1 mm sein. (Außer im Falle an- derslautender Angaben durch Normen und örtliche Gesetze). Die vom Installateur ausgeführten elektrischen Anschlüsse müssen den ...
Página 8
FLAMMKOPFEINSTELLUNG Die Schraube (A) lockern, den Krümmer (B) so verschieben, dass die rückwärtige Fläche (C) der Muffe mit der gewünschten Skala-Einstellzahl übereinstimmt. Die Schraube (A) wieder festziehen. Beispiel: Der Brenner ist auf einem Kessel von 40 kW installiert. S7015 Bei einem Wirkungsgrad von 90% sollte die Brennerleistung ca.
EINSTELLUNG DER VERBRENNUNG In Konformität mit der Wirkungsgradrichtlinie 92/42/EWG muss die Anbringung des Brenners am Heiz- kessel, die Einstellung und die Inbetriebnahme unter Beachtung der Betriebsanleitung des Heizkessels, einschließlich der Kontrolle der Konzentration von CO und CO in den Abgasen, deren Temperatur und der mittleren Wassertemperatur des Heizkessels, ausgeführt werden.
Página 10
LUFTDRUCKWÄCHTER Einstellung des Luftdruckwächter nach Durchführung aller anderen Einstellungen des Brenners mit auf erster Stufe eingestelltem Luft- druckwächter ausführen. Mit Brenner auf verlangter Leistungsstufe langsam den Einstellungssdruck erhöhen, indem Sie den dafür vor- gesehenen Drehgriff im Uhrzeigersinn bis zur Abschaltung des Brenners drehen.
Página 11
BETRIEBSPROGRAMM NORMALBETRIEB LEGENDE – Zündtransformator LED – Anzeige des Betriebsstatus über Entstörtaste t 3d – Gebläsemotor SO – Ionisationsfühler TL – Grenzthermostat – Gasventil AD – Motor zum Klappenöffnen Grün Rot (LED-Anzeige) Erlöschen der Flamme während des Betriebs (erneuter Anlauf max. 3 Versuche) MV = steht Grün (LED-Anzeige) Vorhandensein eines Signals nicht verlangt...
STÖRABSCHALTUNG WEGEN NICHT ERFOLGTER ZÜNDUNG t 3d Rot (LED-Anzeige) Störabschaltung Grün (LED-Anzeige) Grün D7401 LEGENDE STÖRABSCHALTUNG VORHANDENSEIN EINER – Zündtransformator FLAMME ODER FLAMMENSIMULATION WÄHREND DER LED – Anzeige des Betriebsstatus über VORBELÜFTUNG Entstörtaste – Gebläsemotor SO – Ionisationsfühler TL – Grenzthermostat –...
Página 13
FARBCODE DER LED AN DER ENTSTÖRUNGSTASTE DES STEUERGERÄTS Betriebsstatus LED-Farbcode Wartezeit Led aus Vorbelüftung Grün Transformatorzündung Grün Ordnungsgemäße Flamme Grün Nachbelüftung Grün Erneuter Anlauf Grün Dauerbelüftung (*) Grün Vorhandensein der Flamme während des Wartens Led aus Störabschaltung Störabschaltung mit Dauerbelüftung (*) Rot + Grün (*) nur für dazu vorbereitete Anwendungen.
Página 14
Sollte während der Nachbelüftung eine neue Wärmeanfrage erfolgen, so unterbricht sich die Nachbelüftungs- zeit bei der Umschaltung des Grenzthermostat (TL) und es beginnt ein neuer Betriebszyklus des Brenners. Das Steuergerät wird werkseitig mit folgender Einstellung geliefert: 0 Minuten = keine Nachbelüftung. FUNKTION DAUERBELÜFTUNG, (nur für entsprechend vorbereitete Anwendungen) Die Dauerbelüftung ist eine Funktion, bei der die Belüftung unabhängig von der Zündanfrage des Brenners weiter-...
VISUELLE DIAGNOSE DES STEUERGERÄTS Das Steuergerät verfügt über eine Diagnosefunktion, mit der es möglich ist, die eventuellen Ursachen für Funktionsstörungen festzustellen (Anzeige: ROTE LED). Um diese Funktion zu benutzen, muss mindestens 3 Sekunden lang ab dem Augenblick der Störabschal- tung auf die Entstörtaste gedrückt werden (Storabschaltung). Das Steuergerät erzeugt eine Impulssequenz, die sich konstant alle 2 Sekunden wiederholt.
STÖRUNGEN / ABHILFE Nachfolgend finden Sie einige Ursachen und mögliche Abhilfemaßnahmen für eine Reihe von Störungen, die auftreten können und einen Ausfall bzw. nicht ordnungsgemäßen Betrieb des Brenners verursachen können. In den meisten Fällen führt eine Störung zum Aufleuchten der Kontrollleuchte in der Entstörtaste des Steuer- geräts (7, Abb.
Página 17
STÖRUNGEN MÖGLICHE URSACHE ABHILFE Druckwächter ist defekt; austauschen. Der Luftdruckwächter schaltet den Die Störabschaltung Der Luftdruck ist zu gering (Flammkopf Kontakt nicht um. erfolgt während nicht richtig eingestellt). Vorbelüftung. Flamme entsteht. Defekte Ventile: austauschen. Der Gasdruck in der Leitung ist dem am Druckwächter eingestellten Wert sehr nahe.
HINWEISE UND SICHERHEIT Um eine Verbrennung mit niedrigem Schadstoffanteil zu garantieren, müssen die Abmessungen und die Art der Brennkammer des Wärmeerzeugers genau festgelegten Werten entsprechen. Vor der Auswahl eines Brenners für den Einsatz an einem Heizkessel sollte daher vorher eine Beratung beim Kundendienst stattfinden.
Página 20
Declaration of Conformity A.R. 8/1/2004 & 17/7/2009 – Belgium Manufacturer: RIELLO S.p.A. 37045 Legnago (VR) Italy Tel. ++39.0442630111 www.rielloburners.com Distributed by: RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel. (053) 769 030 Fax. (053) 789 440 e-mail. info@riello.be URL. www.riello.be It is hereby certified that the apparatuses specified below conform with the model of the type described n the CE conformity declaration and they are produced and placed in circulation in conformity with the pro- visions defined in L.D.
ENGLISH TECHNICAL DATA TYPE 552T1 15,500 50,000 kcal/h Thermal power 18 – 58 kW – – 7.000 10.340 kcal/Nm 8 – 12 kWh/Nm Natural gas (Family 2) Pressure min. 10 mbar – max. 40 mbar Electrical supply Single phase, 230 V ± 10% 50Hz Motor 0.75 A run current - 2800 rpm.
DIMENSIONS Flange Burner ø D5066 Long combustion head upon request BURNER EQUIPMENT Quantity Description Screws with nuts Insulating gasket Screws for fixing the fairing Grommet Hinge 7 pin plug ACCESSORIES SOFTWARE DIAGNOSTIC KIT A special kit is available that, by an optical link to a PC, shows the burner life together with oper- ating hours, type and number of lockout, serial number, etc...
BOILER FIXING Separate the combustion head from the burner body HINGE ASSEMBLY by removing the nut (1) and pulling back the group (A). Fix the group (B) to the boiler plate (2), inserting the supplied insulating gasket (3). S7392 D5067 FIRING RATE D5135 15,000...
CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT To obtain the maximum output, it is necessary to have 4.6 mbar measured on the pipe coupling, with the combustion chamber at 0 mbar and gas G20 - Pci = 10 kWh/Nm (8,570 kcal/Nm D5136 15,000 20,000...
ELECTRICAL WIRING WARNING: Do not swap neutral and phase over, follow the diagram shown ~ 50Hz 230V carefully and carry out a good earth connection. The section of the conductors must be at least 1 mm . (Unless requested ...
COMBUSTION HEAD ADJUSTMENT Loosen the screw (A), move the elbow (B) so that the rear plate of the coupling (C) coincides with the set point. Tighten the screw (A). Example: The burner is installed in a 40 kW boiler. Considering efficiency of 90% the burner must supply around 44 kW.
COMBUSTION ADJUSTMENT In conformity with Efficiency Directive 92/42/EEC, the application of the burner on the boiler, adjustment and testing must be carried out by observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
AIR PRESSURE SWITCH The air pressure switch is set after all other adjustments have been made. Begin with the switch at the lowest setting. With the burner function at the required power, turn the knob slowly in a clockwise di- rection until burner lockout.
Página 29
OPERATING PROGRAMME NORMAL OPERATION KEY TO LAY-OUT – Ignition transformer LED – Reset button LED indicating operating status t 3d – Fan motor SO – Ionisation probe TL – Limit thermostat – Gas valve AD – Air damper opening motor Green Red (LED lights) Flame loss during operation (Recycle max 3 attempts)
Página 30
LOCKOUT DUE TO FIRING FAILURE t 3d Red (LED lights) Lock-out Green (LED lights) Green D7401 KEY TO LAY-OUT LOCKOUT DUE TO A FLAME OR FLAME SIMULATION – Ignition transformer LED – Reset button LED indicating operating DETECTED DURING PRE-PURGING: status –...
Página 31
COLOUR CODE OF THE CONTROL BOX RESET BUTTON LED Operating status LED colour codes Wait Led unlit Pre-purging Green Transformer turn on Green Regular flame Green Post-purging Green Recycle Green Continuous purging(*) Green Flame present during start up Led unlit Lock-out Lockout with continuous purging (*) Red + Green...
Página 32
CONTINUOUS PURGING FUNCTION, (only for applications in which this is provided for) Continuous purging is an operation that maintains the air purging regardless of whether there is a request for the burner to turn on or not. From the moment it is set, the motor keeps running whether the limit thermostat (TL) has not been switched (burner off), or when the burner is blocked.
Página 33
VISUAL DIAGNOSTICS CONTROL BOX The control box supplied features a diagnostics function through which any causes of malfunctioning can be identified (indicator: RED LED signal). To use this function, you must press and hold the reset button for at least 3 seconds once it has entered the safety condition (lockout).
Página 34
FAULTS / SOLUTIONS Here below you can find some causes and the possible solutions for a series of problems that could cause a failure to start or the poor operation of the burner. A fault in the operation usually switches on the lockout lamp, situated inside the reset button of the control box (7, fig.
Página 35
FAULTS POSSIBLE CAUSES SOLUTION The pressure switch is defective; Replace The air pressure switch does not The burner does not switch The air pressure is too low (combustion pass through the pre- head incorrectly set). purge and locks out. Flame is detected. Defective valves: replace them.
WARNINGS AND SAFETY The dimension of the boiler’s combustion chamber must respond to specific values, in order to guarantee a combustion with the lowest polluting emissions rate. You are therefore advised to consult the Technical Assistance Department before choosing this type of burn- er for the combination with a boiler.
Página 38
Declaración de Conformidad A.R. 8/1/2004 & 17/7/2009 – Bélgica Productor: RIELLO S.p.A. 37045 Legnago (VR) Italy Tel. ++39.0442630111 www.rielloburners.com Puesta en circulación por: RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel. (053) 769 030 Fax. (053) 789 440 e-mail. info@riello.be URL. www.riello.be Con la presente se certifica que la serie de aparatos especificada a continuación es conforme con el...
DIMENSIONES Brida Quemador ø D5066 Cabezal de combustión largo por encargo MATERIAL SUMINISTRADO EN DOTACIÓN Cantidad Descripción Tornillos con tuercas Junta aislante Tornillos para la fijación del envolvente Anillo pasacable Bisagra Conector macho de 7 contactos ACCESORIOS KIT DIAGNOSIS SOFTWARE Está...
FIJACIÓN A LA CALDERA Separe el cabezal de combustión del resto del que- MONTAJE BISAGRA mador quitando la tuerca (1) y retire el grupo (A). Fije el grupo (B) a la placa (2) de la caldera, interpo- niendo la junta aislante (3) suministrada de serie. S7392 D5067 CAMPO DE TRABAJO...
CORRELACIÓN ENTRE PRESIÓN DEL GAS Y POTENCIA Para obtener el máximo rendimiento se necesitan 4,6 mbar medidos en el collarín con la cámara de combustión a 0 mbar y gas G20 - Pci = 10 kWh/m (8.570 kcal/m D5136 15.000 20.000 30.000 40.000...
CONEXIONES ELÉCTRICAS ATENCIÓN: No intercambiar el neutro con la fase; respetar exactamente el es- ~ 50Hz 230V quema indicado y efectuar una buena conexión de tierra. La sección de los conductores debe ser de mín. 1 mm . (Salvo diferentes ...
REGULACIÓN CABEZAL DE COMBUS- TIÓN Afloje el tornillo (A), desplace el codo (B) de manera que el plano trasero del manguito (C) coincida con la marca deseada. Apriete el tornillo (A). Ejemplo: El quemador está instalado en una caldera de 40 S7015 Considerando un rendimiento del 90%, el que- mador deberá...
REGULACIÓN DE LA COMBUSTIÓN De acuerdo con la Directiva de Rendimiento 92/42/EEC la aplicación del quemador a la caldera, el ajuste y la prueba deben realizarse siguiendo el manual de instrucciones de la caldera, inclu- yendo el control de la concentración de CO y CO en los gases de combustión, sus temperaturas y la temperatura media del agua en la caldera.
PRESÓSTATO AIRE Realizar la regulación del presóstato de aire después de haber efec- tuado todas las otras regulaciones del quemador con el presóstato de aire regulado a inicio escala. Con el quemador funcionando a la potencia requerida, girar el botón esférico en el sentido de las agu- jas del reloj hasta el bloqueo del quemador.
Página 47
PROGRAMA DE FUNCIONAMIENTO FUNCIONAMIENTO NORMAL LEYENDA – Transformador de encendido LED – Indicación del estado de funciona- miento desde el botón de desbloqueo t 3d – Motor ventilador SO – Sonda de ionización TL – Termostato límite – Válvula gas AD –...
BLOQUEO POR FALTA DE ENCENDIDO t 3d Rojo (indicación LED) Bloqueo Verde (indicación LED) Verde Rojo D7401 LEYENDA BLOQUEO POR PRESENCIA DE LLAMA O SIMULACIÓN – Transformador de encendido LED – Indicación del estado de funciona- DE LLAMA DURANTE LA PREVENTILACIÓN miento desde el botón de desbloqueo –...
Página 49
CÓDIGO DE COLOR DEL LED DEL PULSADOR DE DESBLOQUEO DE LA CAJA DE CONTROL Estado de funcionamiento Códigos de color LED Espera Led apagado Preventilación Verde Encendido del transformador Verde Llama regular Verde Postventilación Verde Reciclado Verde Ventilación continua (*) Verde Presencia llama durante la espera Led apagado...
Si es necesario calor durante la postventilación, el tiempo de postventilación se puede interrumpir conmutando el termostato límite (TL), y se inicia un nuevo ciclo de funcionamiento del quemador. La caja de control sale de fábrica con los siguientes parámetros: 0 minutos = no post ventilación. FUNCIÓN DE VENTILACIÓN CONTINUA, (sólo para aplicaciones instaladas) La ventilación continua es una función que mantiene la ventilación del aire independientemente de la solicitud de en-...
DIAGNOSIS VISUAL CAJA DE CONTROL La caja de control tiene su propia función de diagnosis mediante la cual es posible detectar fácilmente las posibles causas de mal funcionamiento (indicación: LED ROJO). Para usar dicha función es necesario presionar el pulsador de desbloqueo por lo menos durante 3 segun- dos desde el instante de puesta en seguridad (bloqueo).
Página 52
ANOMALÍAS / SOLUCIONES En la siguiente lista se ofrecen algunas causas de anomalías o averías y sus soluciones, situaciones que se traducen en un funcionamiento anormal del quemador. En la mayoría de los casos una anomalía provoca el encendido de la señal del pulsador de desbloqueo de la caja de control (7, fig. 1, pág. 1). Cuando se enciende dicha señal, es posible volver a poner el quemador en funcionamiento después de pulsar este botón;...
ANOMALÍA POSIBLE CAUSA SOLUCIÓN El presóstato está defectuoso; sustituir- El presóstato aire no conmuta el con- El quemador se blo- tacto. La presión del aire es demasiado baja quea en la fase de pre- (cabezal mal regulado). ventilation No hay presencia de llama. Válvulas defectuosas: sustituirlas.
ADVERTENCIAS Y SEGURIDAD Para garantizar una combustión con la mínima cantidad de emisiones contaminantes, las medidas y el tipo de cámara de combustión del generador de calor deben corresponder a valores bien definidos. Por consiguiente se aconseja consultar al Servicio Técnico de Asistencia antes de escoger este tipo de que- mador para montarlo en una caldera.