Direct Connection

Connect the transducer directly to the Siemens transceiver via the two conductor shielded
cable.
When connecting to a SITRANS LUT400, a SITRANS LUC500, a MultiRanger 100/
Note:
200, or a HydroRanger 200, the white, black, and shield wires are all connected separately.
DO NOT tie the white and shield wires together.
Coaxial Connection
Connect the transducer to the Siemens transceiver via a junction box and RG–62 A/U coaxial
cable. This setup is effective for combined runs up to 365 m (1200 ft).
When connecting to a SITRANS LUT400, a SITRANS LUC500, a MultiRanger 100/
Note:
200, and HydroRanger 200, DO NOT use coaxial cable. See diagram below for proper
procedure.
2-Wire Extension
(for SITRANS LUT400, SITRANS LUC500, MultiRanger 100/200, and HydroRanger
200 only)
wht
A5E32299685
XRS-5 Series Transducers – QUICK START MANUAL
w
b
h
l
t
k
/
/
s
h
h
o
l
t
d
blk
blk
junction box
extend cable using 18 AWG shielded/twisted pair
wht
drain/shield
extend cable using RG-62 A/U coax
drain/shield
Page EN-9