ADJUSTING THE INTERMEDIATE BURNER CAPACITIES
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjusting the intermediate gas flow rates: using a suitable Allen wrench, alter the position of the cam(3) guide
blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out
together with a combustion analysis, to be executed through suitable devices, taking care that the values are the
correct ones and are in accordance with the local safety regulations. The adjustments must be carried out by quali-
fied and skilled technicians authorised by ECOFLAM BRUCIATORI S.p.A..
The adjustment of the position of the firing head is made to obtain
the best combustion performance. When used at the minimum
power output the firing head is move back, whilst is forwarded at
the maximum output. Execution : -loosen the locking screw of
adjusting device A; - move the adjusting device until the desired
position is reached; - tighten the locking screw.
SEZIONE B-
B
COMBUSTION ADJUSTMENT
SETTING THE FIRING HEAD
REMOVING THE NOSEPIECE
POSITION OF ELECTRODES
Ignition electrode
B
A
13
420010250900 BLU 500.1 ÷ 1200.1 PR SW
A
Ionization probe