The VMF-E6 panel can provide a serial communication port to a third party supervisor or BMS. The implemented communication protocol is Modbus RTU; the characteristics
of this connection are:
— Mode of communication: RTU;
— Type of communication: RS485 standard, asynchronous, 1 start bit;
— Speed of communication: 9600/19200/38400 baud;
— Stop bits: 2;
— Parity mode: no mode;
2.1 POINT- POINT BETWEEN AERCONNECT AND VMF-E6
Configuration for this type of connection:
1. Make all the electrical connections correctly (specified in chapter 2.6 p. 10);
2. Configure the parameters relating to the serial port (Modbus address, Baud rate) of the VMF-E6 panel;
3. Activate the webserver recognition and configuration procedure using the "AerConnect Search for devices" (3.2 p. 17) software;