— RTU over TCP/IP: baud rate configured in VMF-E6, TCP port for communication with the gateway and the modbus and IP addresses for every VMF-E6 (max 6).
4. The "Web Server Section" can be used in case of particular situations of use of the LAN network.
5. Specifically, the http port (default 80), the customisable DNS or the default settings for OpenDNS and Google server, the Logout time, and the time zone can be configured.
6. By default, browser access is from the login page "<IP_AERCONNECT>:<HTTP_PORT>\login.html".
4. E.g.: "10.0.0.100\login.html" or "10.0.0.100:80\login.html", also accessible by typing only the IP of the device.
ATTENTION: When AerConnect is started, it uses the language, time and Celsius-Fahrenheit display from the VMF (first query). Then, the time zone set
in the configuration is applied.
WEBSERVER FUNCTIONS
The AerConnect webserver has additional service features, which will be indicated in the paragraphs below.
Reset procedure and default admin:
Directly from the AerConnect device, the factory settings can be reset as follows:
1. Disconnect the device
2. Press the PI button on board and keep it pressed while reconnecting.
3. Wait for the LED B05 signal and then release the button.
After this procedure, LED B00 will indicate incorrect programming.
The button on board also allows the "admin" user password to be reset back to default: "admin". To do so, simply hold down the PI button for at least 10 seconds during normal
operation.
Software update procedure.
There is a manual firmware update mode via USB stick.
To do so, the contents of the P01027FRW12B*.tar.bz2 file must be extracted to the root of the USB key, where at least three files must be present:
P01027RAM01
P01027RAM02.gz
P01027FWR05B001_04-*_AerConnect.ubi