ABB ACH580 Guía Rápida De Puesta En Marcha página 3

Ocultar thumbs Ver también para ACH580:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
Hand-Off-Auto control panel. For complete information on start-up, see ACH580
firmware manual (3AXD50000027537 [English]).
Note: Automatic selection of supply voltage is not supported in ACH580-31. You must
select the supply voltage manually using parameter 95.01. See steps for
Commissioning with parameters
EN – Quick start-up guide
Start-up with the First start assistant on an Hand-Off-Auto
control panel
This guide describes how to start-up the drive using the First start assistant on the
Hand-Off-Auto control panel. For complete information on start-up including Normal ID run,
see ACH580 firmware manual (3AXD50000027537 [English]). Normal ID run is required
during the drive start-up, when the load torque is higher than 20% or the machinery is not
Do not start-up the drive unless you are a qualified electrician.
able to withstand the nominal torque transient during the ID run.
Read and obey the instructions in chapter Safety instructions at the beginning of the
Safety
Hardware manual of the drive. Ignoring the instructions can cause physical injury or death, or
damage to the equipment
Obey the safety instructions in the drive hardware manual. If you ignore them, injury or death, or
Check the installation. See chapter Installation checklist in the Hardware manual of the
damage to the equipment can occur.
drive.
Make sure there is no active start on (DI1 in factory settings, that is, HVAC default).
Make sure that the installation work is complete. Make sure that cover of the drive and the cable box, if
The drive will start up automatically at power-up if the external run command is on
included, are on place. In cabinet drives, make sure that the cabinet doors are closed.
and the drive is in the external control mode.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
• there is a risk of damage in case of an incorrect direction of rotation, or
• a Normal ID run is required during the drive start-up, when the load torque is higher
than 20% or the machinery is not able to withstand the nominal torque transient during
the ID run.
Using the Hand-Off-Auto control panel
The two commands at the bottom of the display
The two commands at the bottom of the display (Options
and Menu in the figure on the right), show the functions of
(Options and Menu in the figure on the right),
the two softkeys
show the functions of the two softkeys
The commands assigned to the softkeys vary depending on
located below the display. The commands
the context.
assigned to the softkeys vary depending on the
Use keys
context.
change values depending on the active view.
Use keys
,
Key
shows a context-sensitive help page.
and/or change values depending on the active
For more information, see ACS-AP-x assistant control panels
user's manual (3AUA0000085685 [Englisch]).
view.
?
Key
shows a context-sensitive help page.
For more information, see ACX-AP-x assistant
control panels user's manual (3AUA0000085685
[English]).
on page 9.
Check that the starting of the motor does not cause any danger. De-couple the driven machine
if there is a risk of damage in case of an incorrect direction of rotation. Before you activate the
automatic fault reset or automatic restart functions of the drive control program, make sure that
no dangerous situations can occur. These functions reset the drive automatically and continue
operation after a fault or supply break. If these functions are activated, the installation must be
clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE
STARTS AUTOMATICALLY".
Hints on using the assistant control panel
and
located below the display.
,
,
and
to move the cursor and/or
,
and
to move the cursor
Safety
and
EN – Quick start-up guide 3
R0-
R4
EN
DA
DE
EN
ES
DE
FI
ES
FI
FR
FR
IT
IT
NL
NL
PT
PL
RU
PT
SV
RU
SV
TR
ZH