Scheduled Replacement Of Worn Components; 6.2.10 Replacing The Capacitor - Sime FUEL 25 EV Manual De Uso, Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
Replace the pump if remains seized or if it resists manual ro-
tation.
To mount the pump back on:
– apply the joint to the pump shaft (4) and insert it in the motor
housing;
– screw the oil pipe onto the housing (1);
– put the connector back onto the solenoid valve housing (2).
a
WARNING
When the burner starts up, check that there are no
leakages from the pump.
6.2.9

Scheduled replacement of worn components

The table below shows the components subject to wear and
their life cycle, at the end of which they should be replaced
exclusively by the SIME Technical Service or by professionally
qualified personnel
Components
Nozzles
Seals
Fuel supply pipes
Flame monitoring systems
Ignition electrodes
Power cable
Magnesium anode

6.2.10 Replacing the capacitor

To replace the capacitor:
– remove the protective cap (1) from the capacitor (2);
1
– disconnect the power supply to the capacitor;
– connect a tester to the Faston terminals of the capacitor; if the
reading is roughly 10% higher than the rated capacity shown
on the capacitor, it means that the capacitor is damaged.
Fig. 51
Life cycle
(years)
1
2
2
3
2
5
1
2
Fig. 52
The value shown in the figure refers to a 4 μF capacitor and is
purely indicative. Please refer to the characteristics of the capa-
citor mounted on the burner.
– Remove the capacitor (2) and replace it
– Mount the components back on by performing the above
steps in reverse order.
m
CAUTION
– After completing the maintenance operations and
mounting the burner back onto the boiler, the bur-
ner must be started up by performing the procedure
described in the chapter "COMMISSIONING".
Fig. 53
61

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fuel 35 ev8118500811850181185028118503

Tabla de contenido