7.1.7 GENIbus address
The GENIbus address of the IO 112 can be set with
the DIP switches 8, 9 and 10. If "Bus configuration,
ID 46" is selected, the address is set automatically
for instance by the MP 204 module.
Switches 8, 9 and 10
GENIbus
7.2 Potentiometer
The potentiometer is used for setting the following
limits:
Analog input and temperature sensor input
• Alarm limit
• Limit 1
• Limit 2.
Counter input
• Alarm limit.
Note: Limits 1 and 2 are not possible for the counter
input.
10
ON
DIP
1 2 3 4 5 6 7 8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
Description
Bus configuration via PC Tool, ID 46.
GENIbus address = ID 48 (unit No 1)
GENIbus address = ID 49 (unit No 2)
GENIbus address = ID 50 (unit No 3)
GENIbus address = ID 51 (unit No 4)
GENIbus address = ID 52 (unit No 5)
GENIbus address = ID 53 (unit No 6)
GENIbus address = ID 54 (unit No 7)
Fig. 6
Potentiometer
When the input (AI, PT or CNT) has been selected,
the indicator light of the selected input will flash.
5 seconds after the limit has been set with the poten-
tiometer, the setting is saved, and the indicator light
will be off. When setting the limits with the potentiom-
eter it is only possible to set the limit to one of the six
specified values.