Product Information; Type Key; Technical Data - Wilo VeroLine-IP-Z Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 45
5

Product information

5.1

Type key

5.2

Technical data

Property
Rated speed
Approved fluids
Permissible min./max. fluid temperature
Max. ambient temperature
Maximum permissible operating pressure 10 bar
Insulation class
Protection class
Pipe connections
Max. anticipated noise level
Electrical connection
1)
Spatial mean value of sound pressure levels on a square measuring surface at a distance of 1 m from the surface of the motor.
Installation and operating instructions Wilo-VeroLine-IP-Z
CAUTION! Risk of property damage!
Non-permitted substances in the fluid can destroy the pump.
Abrasive solids (e.g. sand) increase pump wear.
Pumps without an Ex rating are not suitable for use in potentially
explosive areas.
• The intended use includes complying with these instructions.
• Any other use is considered to be outside the intended use.
The type key consists of the following elements:
Example:
IP-Z 25/6
IP
Screw-end pump as In-line Pump
-Z
Circulation pump
/25
Nominal diameter R/Rp of the pipe connection
6
Power capacity in convergence with max. delivery
head [m]
Value
IP-Z 25/2: 1450 rpm
IP-Z 25/6: 2850 rpm
Drinking water acc. to 2001 drinking
water regulations
Heating water according to VDI 2035
Cooling/cold water
Water-glycol mixtures
(when 20 to 40% glycol vol. and
fluid temperature ≤ 40 °C)
Drinking water acc. to 2001 drinking
water regulations:
0 °C to +80 °C
Heating water according to VDI 2035 or
Cooling water: -8 °C to +110 °C
Water-glycol mixtures
(when 20 to 40% glycol vol.): ≤ 40 °C
+40 °C
F
IP 44 (motor)
IP 54 (terminal box)
Screwed connection Rp1
G1½ thread
1)
50 dB (A)
1~230 V, 50 Hz
3~230 V, 50 Hz
3~400 V, 50 Hz
When ordering spare parts, make sure to state all the information
given on the pump and motor rating plates.
English
Remarks
In short-time duty (2 hours):
To +110 °C
19

Publicidad

Tabla de contenido
loading

Tabla de contenido