en | Configuration
6

Configuration

6.1

Jumper setting

* Default setting
NOTICE!
Adjust the sensitivity of the detector by using the programming
software on the control panel.
Please refer to the software's online help.
6.2

Checking the airflow

Optional:
To ensure that the system is functioning correctly, check that
the air speed enables a sufficient differential pressure to be set
in the device. This can be done by using a manometer. The air
speed in the duct should read between 1.5 m/s and 20 m/s.
The differential pressure between the sample tubes must
measure within the following range:
Minimum
0.25 mm H
O (0.01 in. H
2
0.025 mbar
2.5 Pa
F.01U.033.733 | 5.0 | 2011.11
FAD-420-HS-EN Connection Board
No.
2-3
1-2
FAD-RB-DIBT Relay Board
No.
1-2
2-3
Maximum
O)
4.57 cm H
2
4.48 mbar
448 Pa
Installation guide
Duct Smoke Detector
Configuration
Tamper switch deactivated*
Tamper switch activated
Configuration
Relay drops out if there is no
power and/or the detector C
point is activated.
Relay switches on if the
detector C point is
activated.
O (1.8 in. H
O)
2
2