TECHNICAL SPECIFICATIONS

Power supply (L-N)
Rated power
Photocell power supply output
Output for Vac accessories power
Flashing light output
Courtesy light output
Electric lock output
Gate open warning light output
Antenna input
Encoder
Operating temperature
Accessory fuses
Power supply line fuses
Max. number of transmitters storage
Use in particularly acid, saline or explosive
atmospheres
Protection class
Control unit dimensions
Weight

2.4 - List of cables required

The cables required for connection of the various devices in a
standard system are listed in the cables list table.
The cables used must be suitable for the type of installation; for
ELECTRIC CABLE TECHNICAL SPECIFICATIONS
Connection
Control unit power supply line
Flashing light, courtesy light
Antenna
Electric lock
Transmitter photocells
Receiver photocells
Sensitive edge
Key-switch
Motor power supply line
Encoder power supply line
* If the power supply cable is more than 20 m long, it must be of larger gauge (3x2.5mm
near the automation unit
** Two cables of 2 x 0.5 mm

3 - PRELIMINARY CHECKS

Before installing the product, perform the following checks and
inspections:
check that the gate, the door or the barrier is suitable for automation;
the weight and size of the gate or door and the balance of the barrier
boom must be within the operating limits specified for the automation
system in which the product is installed;
heck that the gate or door has firm, effective mechanical safety
stops;
make sure that the product fixing zone is not subject to flooding;
high acidity or salinity or nearby heat sources might cause the
product to malfunction;
in case of extreme weather conditions (e.g. snow, ice, wide
temperature variations or high temperatures), friction may increase,
causing a corresponding rise in the force needed to operate the
system;
22
CT202 24
maximum 210W
24 Vac without regulation 200 mA / 24 Vdc without regulation 250 mA
cable
1 x cable 3 x 1,5 mm
3 x 0,5 mm
2
1 x cable type RG58
1 x cable 2 x 1 mm
1 x cable 2 x 0,5 mm
1 x cable 4 x 0,5 mm
1 x cable 2 x 0,5 mm
1 x cable 4 x 0,5 mm
1 x cable 2 x 1,5 mm
1 x cable 3 x 0,5 mm
can be used as an alternative
2
CT202 24E
230Vac (+10% - 15%) 50/60 Hz
maximum 280W
24Vdc (without regulation) maximum 250mA
24Vdc (without regulation) 15W
24Vdc (without regulation) 15W
12Vac 15VA maximum
24Vdc (without regulation) 5W
50Ω type cable RG58
no
-20°C + 55°C
1.6AT
222 x 110 x 275 mm
3,93 kg
example, an H03VV-F type cable is recommended for indoor
applications, while H07RN-F is suitable for outdoor applications.
2
**
2
2
2
2
**
2
2
2
) and a safety grounding system must be installed
2
the starting torque may therefore exceed that required in normal
conditions;
check that when operated by hand the gate, the door or the barrier
moves smoothly without any areas of greater friction or derailment
risk;
check that the gate, door or the barrier is well balanced and will
therefore remain stationery when released in any position;
check that the electricity supply line to which the product is to be
connected is suitably earthed and protected by an overload and
differential safety breaker device;
he system power supply line must include a circuit breaker device
with a contact gap allowing complete disconnection in the conditions
specified by class III overvoltage;
ensure that all the material used for installation complies with the
relevant regulatory standards.
CT202 24L
115Vac (+10%-15%) 50/60 Hz
maximum 210W
yes
2AT
3.15AT
150
NO
IP54
maximum allowable limit
20 m *
20 m
20 m (advised < 5 m)
10 m
20 m
20 m
20 m
20 m
10 m
10 m
no