How to open the valve
Open or close the valve.
Liquid side, gas side
Open the valve with hexagon wrench.
[Hexagonal wrench is required.]
Hexagonal wrench size
Liquid side
Gas side
SM56
4 mm
4 mm
SM80
4 mm
5 mm
Valve handling precautions
Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force.
Securely tighten the cap with a torque wrench.
Cap tightening torque
14 to 18
Ø6.4 mm
(1.4 to 1.8 kgf m)
14 to 18
Ø9.5 mm
(1.4 to 1.8 kgf m)
Valve size
33 to 42
Ø12.7 mm
(3.3 to 4.2 kgf m)
33 to 42
Ø15.9 mm
(3.3 to 4.2 kgf m)
14 to 18
Charge port
(1.4 to 1.8 kgf m)
69-EN
1115150101_EN.indd 35
1115150101_EN.indd 35
Replenishing refrigerant
This model is a 20 m chargeless type that does not
need to have its refrigerant replenished for refrigerant
pipes up to 20 m. When a refrigerant pipe longer than
20 m is used, add the specified amount of refrigerant.
Refrigerant replenishing procedure
1. After vacuuming the refrigerant pipe, close the
valves and then charge the refrigerant while the air
conditioner is not working.
2. When the refrigerant cannot be charged to the
specified amount, charge the required amount of
refrigerant from the charge port of the valve on the
gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the
refrigerant composition varies, which disables normal
operation.
Adding additional refrigerant
21~30 m: L
SM56
20 g × (L-20)
SM80
40 g × (L-20)
L: Pipe length
The refrigerant need not be reduced for a 20 meter
(or less) refrigerant pipe.
– 35 –
7

Electrical work

CAUTION
An installation fuse must be used for the power supply
line of this air conditioner.
Incorrect / incomplete wiring may lead to an electrical
fire or smoke.
Prepare an exclusive power supply for the air
conditioner.
This product can be connected to the mains power.
Fixed wire connections:
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the fixed wiring.
Be sure to use the cord clamps attached to the
product.
Do not damage or scratch the conductive core or inner
insulator of the power and system interconnection
wires when peeling them.
Use the power and system interconnection wires with
specified thicknesses, specified types and protective
devices required.
1
Remove valve cover screw.
2
Pull the valve cover downward to remove it.
Valve cover
Power supply wire
System
interconnection
wires
Wiring between indoor unit
and outdoor unit
The dashed lines show on-site wiring.
(System
(Main circuit)
interconnection wires)
L
1
1
Input power
N
2
2
Remote
3
3
controller
Outdoor unit
Indoor unit
Earth
Circuit
breaker
Connect the system interconnection wires to the
identical terminal numbers on the terminal block of
each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the
following specifications.
Model RAV-
SM56, SM80
220-240 V~, 50 Hz
Power supply
220 V~, 60 Hz
Maximum running current
15.5 A
Installation fuse rating
20 A (all types can be used)
H07 RN-F or 60245 IEC 66
Power supply wire
(2.5 mm
2
or more)
System interconnection
H07 RN-F or 60245 IEC 66
wires
2
(1.5 mm
or more)
8/24/13 9:40 AM
8/24/13 9:40 AM
70-EN