Air conditioner operating conditions

For proper performance, operate the air conditioner under the following temperature conditions:
Cooling operation
Dry bulb temp.
Heating operation
Wet bulb temp.
If air conditioner is used outside of the above conditions, safety protection may work.
13

Functions to be implemented locally

Handling existing pipe
When using the existing pipe, carefully check for the following:
Wall thickness (within the specified range)
Scratches and dents
Water, oil, dirt, or dust in the pipe
Flare looseness and leakage from welds
Deterioration of copper pipe and heat insulator
Cautions for using existing pipe
Do not reuse a flare nut to prevent gas leaks.
Replace it with the supplied flare nut and then process it to a flare.
Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much
residue is discharged, wash the pipe.
Check welds, if any, on the pipe for gas leaks.
When the pipe corresponds to any of the following, do not use it. Install a new pipe instead.
The pipe has been opened (disconnected from indoor unit or outdoor unit) for a long period.
The pipe has been connected to an outdoor unit that does not use refrigerant R22, R410A or R407C.
The existing pipe must have a wall thickness equal to or larger than the following thicknesses.
Reference outside
Wall thickness (mm)
diameter (mm)
Ø
6
4 .
0
8 .
Ø
9
5 .
0
8 .
Ø
1
2
7 .
0
8 .
Ø
1
5
9 .
1
0 .
Ø
1
9
0 .
1
0 .
Do not use any pipe with a wall thickness less than these thicknesses due to insufficient pressure capacity.
73-EN
1115150101_EN.indd 37
1115150101_EN.indd 37
–15 °C to 46 °C
–15 °C to 15 °C
– 37 –
Refrigerant recovery
When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit, the recovery
operation can be performed by operating the SW01 and SW02 switches on the P.C. board of the outdoor unit.
A cover for the electric parts has been installed in order to provide protection from electric shocks while work is
being performed. Operate the service switches and check the LED displays with this electric parts cover in place.
Do not remove this cover while the power is still on.
DANGER
The entire P.C. board of this air conditioner system is a high-voltage area.
When operating the service switches with the power of the system left on, wear electrically insulated gloves.
LED displays
D800
D801
D802
D803
D804
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green)
There are four LEDs display patterns.
: ON
: OFF
: Rapid flashing (5 times/sec.)
: Slow flashing (1 time/sec.)
In the initial LED display status, D805 is lighted as shown on the right. If the initial status is not established (if
D805 is flashing), hold down the SW01 and SW02 service switches simultaneously for at least 5 seconds to
return the LED displays to the initial status.
D800
D801
(Yellow)
(Yellow)
or
or
Rapid
Rapid
OFF
or
OFF
or
OFF
flashing
flashing
Service switches
D805
LED display initial status
D802
D803
D804
(Yellow)
(Yellow)
(Yellow)
or
or
or
Rapid
Rapid
Rapid
or
OFF
or
OFF
or
flashing
flashing
flashing
SW01, SW02
D805
(Green)
ON
74-EN
8/24/13 9:40 AM
8/24/13 9:40 AM