Basic Operation
Other UPS Features (Rear Panel)
AC Receptacles: Your UPS features 15-amp AC outlets, and select models also
feature 20-amp and 30- amp AC outlets. These output receptacles provide your
connected equipment with AC line power during normal operation and battery
power during blackouts and brownouts. The UPS protects equipment connected
to these receptacles against damaging surges and line noise. If you have a seri-
al or USB connection to your UPS, you can remotely reboot connected equipment
15 amp/120V
by turning the receptacles OFF and ON using Tripp Lite's PowerAlert Software.
NEMA 5-15R
Select models have their receptacles divided into one or more load banks
(labelled "LOAD 1," etc.) which maybe be remotely switched OFF and ON using
Tripp Lite UPS software without interrupting power to equipment connected to
the other outlets. Select models also feature outlets labelled "UNSWITCHED",
which may not be remotely switched off. See software instructions for details.
20 amp/120V
NEMA 5-20R
30 amp/120V
NEMA L5-30R
NEMA L5-20R
Smart Serial Port(s): Your UPS features 1 or more serial ports that may be
used to connect the UPS to a serial port on any workstation or server. Use with
Tripp Lite cabling and PowerAlert Software to monitor and manage network
power and automatically save open files and shut down equipment during a
blackout. See Connection section.
Smart USB Port(s): Your UPS features 1 or more USB ports that may be used to
connect the UPS to a USB port on any workstation or server. Use with Tripp Lite
cabling and PowerAlert Software to monitor and manage network power and
automatically save open files and shut down equipment during a blackout. See
Connection.
EPO (Emergency Power Off) Port: Your UPS features a EPO port that may
be used to connect the UPS to a contact closure switch to enable emergency
inverter shutdown. See Connection.
Accessory Slot: Remove the small cover panel from this slot to install optional
accessories to remotely monitor and control your UPS. Refer to your accessory's
manual for installation instructions. Contact Tripp Lite Customer Support at
(773) 869-1234 for more information, including a list of available SNMP, network
management and connectivity products.
continued
20 amp/120V
10