3.3
TERMINAL BOARD M3
3.3.1 Opening limit switch
Terminals "10-11" (Circuit Normally Closed). The status of this input is signalled by the FCA LED. This circuit is connected
to the opening limit switch. This circuit has a delay of one second, i.e. once the limit switch is pressed, the barrier slows
down for one second.
3.3.2 Closing limit switch
Terminals "9-11" (Circuit Normally Closed). The status of this input is signalled by the FCC LED. This circuit is connected
to the closing limit switch. This circuit has a delay of one second, i.e. once the limit switch is pressed, the barrier slows
down for one second.
3.3.3 Closing protection photocells
Terminals "8-11" (Circuit Normally Closed). The status of this input is signalled by the FOTO LED. This circuit is connected
to any safety device (photocells, pressure switch, detector, etc.) which, when a contact is opened, acts as a safety on
the closing motion. The effect will opening will vary depending on the settings performed using dip-sw 3.
Note: To install multiple safety devices connect the NC contacts in series.
3.4
TERMINAL BOARD M4
3.4.1 Start
Terminals "6-7" (Circuit Normally Open). The status of this input is signalled by the START LED. This circuit is connected
to any device (e.g. button, radio control, etc.) which, when a contact is closed, generates a barrier opening and/or
closing pulse.
Note: To install multiple pulse devices connect the contacts in parallel. It is possible to block the barrier from closing
again by connecting a 24h timer in parallel to the START circuit.
3.4.2 Stop
Terminals "5-7" (Circuit Normally Closed). The status of this input is signalled by the STOP LED. This circuit is connected
to any device (e.g. button) which, when a contact is opened, stops the barrier motion.
Note: If STOP devices are not connected, jump connect the input. To install multiple STOP devices, connect the NC
contacts in series.
3.4.3 Accessory power supply
Terminals "3-4". (24 Vdc). Warning: the max. load for the accessories is 500 mA.
4. INSERTING THE REMOTE CONTROL RECEIVER BOARD
The unit is designed to house a single channel radio-receiver module. To install the module, cut off the electric power
supply and insert the module into the special connector M5 inside the unit. Then follow the radio-receiver instructions
to memorise the remote control.
The unit is designed to house a motor control module (optional). To install the module, cut off the electric power supply
and insert the module into the special connector M6 inside the unit. If the barrier strikes an obstacle, this module blocks,
reverses the barrier motion for 0.5 seconds and inhibits the unit, as signalled by the fast flashing of the WORK LED. Only
after the obstacle has been removed followed by the START control will the unit allow the barrier to continue the set
cycle.
LEDS
STOP
START
FOTO - Photocell
FCC - Closing limit switch
FCA - Opening limit switch
Note: Bold is used to indicate the led condition with the barrier at rest.
7.1 PAUSE
To adjust the pause duration (for automatic operation), use "BREAK" trimmer.
The duration can be adjusted from 2 to 90 seconds.
5. INSERTING THE MOTOR CONTROL MODULE

6. CONTROL LEDS

ON
Control deactivated
Control activated
Safety devices disabled
Limit switch disabled
Limit switch disabled
7. ADJUSTMENTS WITH TRIMMER
OFF
Control activated
Control deactivated
Safety devices enabled
Limit switch enabled
Limit switch enabled
6
LED WORKS
On: barrier moving
Off: barrier at rest
Fast flashing:
incorrect motor connection,
electronic clutch malfunction or
control module activated